Appendix m – long term blower storage – AERCO BMK 6000 User Manual

Page 203

Advertising
background image

Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

APPENDIX M – LONG TERM BLOWER STORAGE

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 203 of 210

GF-133

Ph.: 800-526-0288

03/20/14

APPENDIX M – LONG TERM BLOWER STORAGE

If the Blower is left in long term storage (exceeding 30 days after receipt of equipment), damage
can result. In the event that the Blower is to be kept in storage exceeding 30 days, you must you
must complete the instructions below.

NOTE

Failure to adhere to the instructions below voids all warranties in their
entirety.

LONG-TERM STORAGE INSTRUCTIONS

1. Select a suitable storage site:

• Level, well-drained, firm surface, in clean, dry and warm location. Minimum

temperature of 50°F (10°C).

• Isolated from possibility of physical damage from construction vehicles, erection

equipment, etc.

• Accessible for periodical inspection and maintenance.

2. The blower should be supported under each corner of its base to allow it to “breath”.

Supports (2 x 4’s, timbers, or railroad ties) should be placed diagonally under each corner.

3. If the equipment is to be stored for more than three (3) months, the entire blower

assembly must be loosely covered with plastic, but not tightly wrapped.

4. Storage Maintenance:

NOTE

A periodic inspection and maintenance log, by date and action taken, must
be developed and maintained for each blower. See example below. Each
item must be checked monthly.

Example Storage / Maintenance Schedule Log

Item

Action

Dates Checked

1

Re-inspect units to insure any protective devices used
are functioning properly. Check for scratches in the
finish which will allow corrosion or rust to form

2

Rotate wheel a minimum of 10 full revolutions to keep
the motor bearing grease from separating and drying
out.

THIS STEP IS CRITICAL.

Advertising