6.11 IGNITION SWITCH OPEN DURING IGNITION

The Ignition Switch (and the Purge Switch) is located on the Air/Fuel Valve. To check the switch,
proceed as follows:

Ignition Switch Open During Ignition

1. Set the unit’s ON/OFF switch to the OFF position.

2. Place the unit in Manual Mode and set the valve position between 25% and 30%.

3. Remove the Air/Fuel Valve cover (Figure 6-7) by rotating the cover counterclockwise to

unlock and lift up to remove.

4. Remove one of the two wires (#169 or #170) from the Ignition Switch (Figure 6-8).

5. Initiate a unit start sequence.

6. The unit should begin its start sequence and then shut down and display IGN SWITCH

OPEN DURING IGNITION.

7. Replace the wire on the Ignition Switch and press the CLEAR button. The unit should

restart.

Stepper Motor

Purge Position
Switch

Ignition Position
Switch

Dial

AIR IN