Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

Page 54 of 210

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0086_0D

03/20/14

Ph.: 800-526-0288

GF-133

BMK 6000 Function Timing Chart For Proved Pilot Control System

OPERATING STATE

STANDBY

C-MORE

PRE-PURGE

PFEP

MFEP

RUN

COMPONENT

T=0s 30≤T≤60s

T= 7 sec

C-MORE CONTROL BOX

Scanner Power

Ignition Power

SSOV Power

PILOT VALVE

Pilot Valve Closed

Pilot Valve Open

IGNITION TRANSFORMER

Transformer Off

Transformer On

UV SCANNER

Powered

"Ignored"

In Use

RELAY 1 (R1)

Coil

C-NC

C-NO

RELAY 2 (R2)

Coil Power from R1

Coil Power from SKP 15 AUX

C-NC

C-NO

UPSTREAM SSOV (SKP15)

Power through R1

Power through R2 and AUX

POC C-NC

POC C-NO

AUX C-NC

AUX C-NO

DOWNSTREAM SSOV (SKP25)

Power through R1

Power through R2 and AUX

POC C-NC

POC C-NO

Figure 3-7: Timing Chart For Proved Pilot System