Low Gas Pressure Fault Test – Continued

9. Upon test completion, close the external ball valve to shut down the unit. Remove the

manometer and NPT-to-barbed fitting. Replace the 1/4“ plug removed in step 1.

6.3 HIGH GAS PRESSURE FAULT TEST

To simulate a high gas pressure fault, refer to Figure 6-1B and perform the following steps:

Figure 6-1B: High Gas Pressure Test

High Gas Pressure Fault Test

1. Remove the 1/4“ plug from the ball valve shown in Figure 6-1B.

2. Install a NPT-to-barbed fitting and a 0 – 16” W.C. manometer where the 1/4” plug was

removed. Open the ball valve at the High Gas Pressure switch.

3. Open the external gas supply ball valve upstream of the unit.

4. Start the unit in the Manual mode at a valve position (% open) between 25 and 30%.

5. With the unit running, monitor the gas pressure on the manometer installed in step 2 and

record the gas pressure reading.

TO AIR/FUEL

VALVE

GAS

INLET

DOWNSTREAM LOW

GAS PRESSURE

SWITCH (6.9” W.C.)

HIGH GAS

PRESSURE

SWITCH

(10.5” W.C.)

MANUAL SHUT-OFF VALVE

UPSTREAM LOW GAS
PRESSURE SWITCH (8.5” W.C.)

BALL VALVE WITH 1/4" NPT PLUG
(Install manometer here for High Gas Pressure test)