Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 7 – MAINTENANCE

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 95 of 210

GF-133

Ph.: 800-526-0288

03/20/14

Figure 7-2: O

2

Sensor Mounting Location

7.5 COMBUSTION CALIBRATION & PILOT REGULATOR ADJUSTMENT

Combustion settings must be checked at the intervals shown in Table 7-1 as part of the
maintenance requirements. Refer to Chapter 4 for combustion calibration instructions. Pilot
Regulator tests and adjustments are performed using the procedures in sections 7.5.1 and 7.5.2
which follow.

7.5.1 Pilot Regulator Pressure Testing

The BMK6000 unit has a Pilot Regulator system in the gas train that should be pressure tested
annually as described in the following procedure. However, if the pressure is above 5.0” W.C. or
below 4.0” W.C., then the Pilot pressure regulator must be recalibrated using the instructions
provided in section 7.5.2.

The Pilot Regulator pressure test is performed as follows:

O

2

SENSOR

GAS SUCTION

LINE FROM

EXHAUST

MANIFOLD

EXHAUST

MANIFOLD