Appendix e – boiler default settings – AERCO BMK 1000 User Manual

Page 155

Advertising
background image

Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

APPENDIX E – BOILER DEFAULT SETTINGS

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 155 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

APPENDIX E – BOILER DEFAULT SETTINGS

MENU & OPTION

FACTORY DEFAULT

Setup Menu

Password

0

Language

English

Unit of Temp

Fahrenheit

Comm Address

0

Baud Rate

9600

Configuration Menu

Internal Setpt

130°F

Unit Type

BMK Boiler LN

Unit Size

750 MBH or 1000 MBH

Fuel Type

Natural Gas

Boiler Mode

Constant Setpoint

Remote Signal (If Mode = Remote
Setpoint, Direct Drive or Combination)

4 – 20 mA / 1-5V

Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)

70°F

Reset Ratio
(If Boiler Mode = Outdoor Reset)

1.2

Outdoor Sensor

Disabled

System Start Tmp
(If Outdoor Sensor = Enabled)

60°F

Setpt Lo Limit

60°F

Setpt Hi Limit

195°F

Temp Hi Limit

195°F

Max Valve Position

100%

Pump Delay Timer

0 min

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

Analog Output

Valve Position 0-10V
CAUTION: DO NOT Change

Lo Fire Timer

2 sec


Advertising
This manual is related to the following products: