Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 51 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

Figure 3-3: SSOV Location

3.

With all required safety device switches closed, a purge cycle will be initiated and the
following events will occur:

a) The Blower relay energizes and turns on the blower.

b) The Air/Fuel Valve rotates to the full-open purge position and closes purge position

switch. The dial on the Air/Fuel Valve (Figure 3-4) will read 100 to indicate that it is
full-open (100%).

c) The VALVE POSITION bargraph will show 100%.

Figure 3-4: Air/Fuel Valve In Purge Position

SSOV

GAS INLET

TO AIR/FUEL
VALVE

MANUAL
SHUT-OFF VALVE

STEPPER MOTOR

TO

BLOWER

AIR

INLET

100