APPENDIX M – ULTRA-LOW NOx CALIBRATION

Page 186 of 192

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0082_0J

05/21/2014

Ph.: 800-526-0288

GF-130

Ultra-Low NOx Natural Gas Combustion Calibration – Continued

Figure M-1. Gas Pressure Adjustment Screw Location

11.

Using the ▲ arrow key, increase the valve open position to 100%. Verify that the gas pressure
on the downstream side of the SSOV settles within the range of 2.0 ± 0.4” W.C. Readjust the
gas pressure if necessary.

12. With the valve position at 100%, insert the combustion analyzer probe into the flue probe

opening and allow enough time for the combustion analyzer reading to stabilize.

13. Compare the oxygen readings on the combustion analyzer to the on-board O

2

sensor value

displayed in the Operating Menu of the C-More Control Panel. If the values differ by more
than ±0.5%, have your combustion analyzer calibration checked as soon as possible. If the
readings differ by more than ±1.5%, use the on-board O

2

sensor to calibrate the unit. Have

your combustion analyzer serviced.

14. Compare the measured oxygen level to the oxygen range shown below. Also, ensure that

the nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the values
shown.

Ultra-Low NOx Combustion Calibration Readings

Valve Position

Oxygen (O

2

) %

Nitrogen Oxide

(NOx)

Carbon Monoxide

(CO)

100%

5% - 7%

<9 ppm

<100 ppm

15. If the oxygen level is not within the required tolerance, the gas pressure on the downstream

side of the SSOV must be adjusted using the gas pressure adjustment screw on the SSOV
(Figure L-1). Slowly rotate the gas pressure adjustment (approximately 1/4-turn increments).
Allow the combustion analyzer to stabilize following each adjustment. Clockwise rotation
reduces the oxygen level, while counterclockwise rotation increases the oxygen level.

16. Once the oxygen level is within the specified range at 100%, record the O

2

, NOx and CO

readings on the Combustion Calibration Data Sheets provided with the unit.

TYPICAL SSOV ACTUATOR WITH REGULATOR

BRASS HEAD CAP

(Remove to access gas

pressure adjustment

screw)