APPENDIX J – RECOMMENDED PERIODIC TESTING

Page 180 of 192

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0082_0J

05/21/2014

Ph.: 800-526-0288

GF-130

Item

Frequency

Accomplished

By

Remarks

Low air flow

Monthly

Operator

See section 6.8

High and low gas
pressure interlocks

Monthly

Operator

See sections 6.2 and 6.3

Air/Fuel Valve purge
position switch

Annually

Service

Technician

See section 6.10

Air/Fuel Valve ignition
position switch

Annually

Service

Technician

See section 6.11

Safety valves

As required

Operator

Check per A.S.M.E. Boiler and Pressure
Vessel Code, Section IV

Inspect burner
components

Semi-

Annually

Service

Technician

See section 7.7

Condensate Trap

Semi-

Annually

Operator

See section 7.8

Oxygen (O

2

) Level

Monthly

Operator

Verify oxygen level is between 3% and 8%
during boiler operation