PROPANE Combustion Calibration –

Continued

27.

Once the oxygen level is within the specified range at 80%, press the ENTER key to
store the selected blower output voltage for the 80% valve position. Record all readings
on the Combustion Calibration Sheets provided.

28.

Repeat steps 20 through 27 for valve positions of 60%, 45%, 30% and 18%* (see *NOTE
below). The oxygen (O

2

), nitrogen oxide (NOx) and carbon monoxide (CO) should remain

within the same limits for all valve positions as shown in the following table.

*NOTE

Set the Valve Position at 18% but make adjustments to the Combustion
Calibration value designated as 16%.

NOTE

If NOx readings exceed the target values shown (<30 ppm), increase the
O

2

level up to 1% higher than the listed calibration range shown in the

table. Record the increased O

2

value on the Combustion Calibration sheet.

Propane Combustion Calibration Readings

Valve Position

Oxygen (O

2

) %

Nitrogen Oxide

(NOx)

Carbon Monoxide

(CO)

60%

5% - 6%

<30 ppm

<100 ppm

45%

5% - 6%

<30 ppm

<100 ppm

30%

5.8% - 6.8%

<30 ppm

<100 ppm

18%

5% - 6%

<30 ppm

<100 ppm

29.

If the oxygen level at the 18% valve position is too high and the Blower voltage is at the
minimum value, you can adjust the idle screw (TAC valve) which is recessed in the top of
the Air/Fuel Valve (see Appendix G). Rotate the screw 1/2 turn clockwise (CW) to add fuel
and reduce the O

2

to the specified level. Recalibration MUST be performed again from

60% down to 18% after making a change to the idle screw (TAC valve).

30.

This completes the PROPANE combustion calibration procedures.

4.5 REASSEMBLY AFTER COMBUSTION CALIBRATION

Once the combustion calibration adjustments are properly set, the unit can be reassembled for
service operation.

Reassembly After Combustion Calibration

1.

Set the ON/OFF switch in the OFF position.

2.

Disconnect AC power from the unit.

3.

Shut off the gas supply to the unit.

4.

Remove the manometer and barbed fittings and reinstall the NPT plug using a suitable
pipe thread compound.