Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

Page 46 of 192

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0082_0J

05/21/2014

Ph.: 800-526-0288

GF-130

Table 3-4: Configuration Menu - Continued

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Max Valve Position

40%

100%

100%

Pump Delay Timer

0 min.

30 min.

0 min.

Aux Start On Dly

0 sec.

120 sec.

0 sec.

Failsafe Mode

Shutdown or Constant Setpt

Shutdown

Low Fire Timer

2 sec.

600 sec.

2 sec.

Setpt Limiting

Enabled or Disabled

Disabled

Setpt Limit Band

0°F

10°F

0

Network Timeout

5 Sec

999 Sec

30 Sec

HI DB Setpt EN

0%

100%

30%

Demand Offsert

0

25

0

Deadband High

0

25

0

Deadband Low

0

25

0

Spark Monitor

Enabled or Disabled

Disabled

Spark Current

Display

DO NOT CHANGE the Analog Output Menu Item from its Default
setting (Valve Position 0-10V).

3.7 TUNING MENU

The Tuning Menu items shown in Table 3-5 are Factory set for each individual unit. Do not
change these menu entries unless specifically requested to do so by Factory-Trained personnel.

Table 3-5: Tuning Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Prop Band

1°F

120°F

8°F

Integral Gain

0.00

2.00

1.6

Derivative Time

0.0 min

2.00 min

0.10 min

Warmup Prop Band

0°F

120°F

95°F

Warmup Int Gain

0

2.00

0.50

Warmup PID timer

0 sec.

240 sec.

20 sec.

Reset Defaults?

Yes, No, Are You Sure?

No

CAUTION