APPENDIX M – ULTRA-LOW NOx CALIBRATION

Page 188 of 192

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0082_0J

05/21/2014

Ph.: 800-526-0288

GF-130

Ultra-Low NOx Natural Gas Combustion Calibration – Continued

NOTE

If NOx readings exceed the target values shown (<9 ppm), increase the O

2

level up to

1% higher than the listed calibration range shown in the table. Record the increased O

2

value on the Combustion Calibration sheet.

Ultra-Low NOx Combustion Calibration Readings

Valve Position

Oxygen (O

2

) %

Nitrogen Oxide

(NOx)

Carbon Monoxide

(CO)

60%

5% - 7%

<9 ppm

<100 ppm

45%

5% - 7%

<9 ppm

<100 ppm

30%

5% - 7%

<9 ppm

<100 ppm

18%

5% - 7%

<9 ppm

<100 ppm

29. If the oxygen level at the 18% valve position is too high and the Blower voltage is at the

minimum value, you can adjust the idle screw (TAC valve) which is recessed in the top of
the Air/Fuel Valve (see Appendix G). Rotate the screw 1/2 turn clockwise (CW) to add fuel
and reduce the O

2

to the specified level. Recalibration MUST be performed again from 60%

down to 18% after making a change to the idle screw (TAC valve).

30. This completes the ultra-low NOx Natural Gas combustion calibration procedures.

M-2. REASSEMBLY

Once the combustion calibration adjustments are properly set, the unit can be reassembled for
service operation.

Reassembly

1. Set the ON/OFF switch to the OFF position.

2. Disconnect AC power from the unit.

3. Shut off the gas supply to the unit.

4. Remove the manometer and barbed fittings and reinstall the NPT plug using a suitable pipe

thread compound.

5. Remove the combustion analyzer probe from the 1/4” vent hole in the exhaust manifold.

Replace the 1/4” NPT plug in the manifold.

6. Replace all previously removed sheet metal enclosures on the unit.