Page 13

FORMAT SELECTIONS

DATA

FORMAT

DESCRIPTION

0


Local


Communicator is disabled

1


Universal 4+2


Two digit event code 1800hz transmit 2300hz handshake double round parity
40pps

2


3+1 fast (or 4+1)


One digit event code 1900Hz transmit 1400Hz handshake double round parity
20pps

3


Reserved


Reserved

4


Pager


2 digit event code DTMF transmission

5


3/1 or 4/1 slow


1800hz transmit 2300hz handshake double round parity 20 p.p.s. hex capability

6


3/1 or 4/1 slow


1800hz transmit 1400hz handshake double round parity 20 p.p.s. hex capability

7


3/1 or 4/1 fast


1800hz transmit 2300hz handshake double round parity 40 p.p.s. hex capability

8


3/1 or 4/1 fast


1800hz transmit 1400hz handshake double round parity 40 p.p.s. hex capability

9


3/1 or 4/1 fast with
parity


1800hz transmit 2300hz handshake single round w/parity 40 p.p.s. hex capability

10


3/1 or 4/1 fast with
parity


1800hz transmit 1400hz handshake single round w/parity 40 p.p.s. hex capability

11


4+2 express


2 digit event code DTMF transmission

12


4+2 fast


Two-digit event code 1900hz transmit 1400hz handshake double round parity 20
p.p.s.

13


Ademco Contact ID


DTMF (see pages 33-34)

14


SIA


FSK (see pages 33-34)

15


Custom format


(See location 18, page 16)



REPORTING EVENTS TO PHONE NUMBER 1


Location 4 is used to select which events are reported to Phone #1. If dual or split reporting is not desired, location 4
should be used to select all events to Phone #1. If dual or split reporting is desired, location 4 should be used to select
only those events that should be reported to Phone #1. If no events should be reported to Phone #1, location 4
should be programmed as "0" (disabled).

LOCATION 4 - EVENTS REPORTED TO PHONE # 1 (2 segments, feature selection data)

Segment 1:

1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Bell Cut Restore.
7 = Test Reports.
8 = Start and End programming, Download complete.

Segment 2:

1 = Zone and Box Tamper and Tamper Restore.
2 = Auxiliary Power Over-current and Restore.
3 = Wireless Sensor Missing and Restore.
4 = Wireless Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Reserved.
8 = Reserved.