NX-4 Control


Page 25

LOCATIONS 112 THRU 149 contain the remaining 19 Customized Zone Group information. The even numbered
locations reflect the

AGroup Alarm Event Code@ and the odd numbered locations designate the Group Characteristics.

Locations 112 and 113 correspond to Group 2; Locations 148 and 149 correspond to Group 20. Use the description
found in Location 110 for programming the Alarm Event Codes, and use Table 1.1 shown on page 24 to select the
Group Characteristics. Refer also to the Programming Worksheets.

Table 2.1 STANDARD ZONE TYPES (Default Configurations)

Zones can be programmed to be one of twenty different zone types (configurations). Zone types # 17 - 20 can be
used for wireless or hardwired zones using European double EOL configuration. The default zone types are listed
below. If none of the following zone types meet your needs, these configurations can be customized by programming
locations 110-149.

DATA

DESCRIPTION OF STANDARD ZONE TYPES

"1"

DAY ZONE - Instant when system is armed trouble zone when system is disarmed.

"2"

24-HOUR AUDIBLE - Creates an instant yelping siren alarm regardless of the armed state of the panel.

"3"

ENTRY/EXIT DELAY 1- A trip will start entry delay 1. The lack of a trip during exit delay will enable the Automatic
Bypass or Instant mode if so programmed.

"4"

FOLLOWER WITH AUTO- BYPASS DISABLED - This zone will be instant when the system is armed and no entry or exit
delays are being timed. It is delayed during entry and exit delay times. This zone will not automatically bypass even if
enabled in Segment 1 of Location 23.

"5"

INTERIOR FOLLOWER WITH AUTO- BYPASS ENABLED - This zone will be instant when the system is armed and no
entry or exit delay is being timed. It is delayed during entry and exit delay times. This zone will automatically bypass if
enabled in Segment 1 of Location 23.

"6"

INSTANT - This zone creates an instant alarm whenever it is tripped and the Armed LED is on.

"7"

24-HOUR SILENT - Creates an instant silent alarm regardless of the armed state of the control panel. It will not display
on the keypad.

"8"

FIRE - This zone will light the Fire LED and sound the temporal siren each time the zone is shorted. It will also rapidly
flash the Fire LED indicating a trouble if the zone is open.

"9"

ENTRY/EXIT DELAY 2- A trip will start entry delay 2. The lack of a trip during exit delay will enable the Automatic
Bypass or Instant mode if so programmed.

"10"

24-HOUR SILENT SUPERVISED- Creates an instant silent alarm regardless of the armed state of the control panel. It
will display on the keypad.

"11"

RESERVED

"12"

INTERIOR FOLLOWER WITH "CROSS ZONE" ENABLED - This zone will be instant when the system is armed and no
entry or exit delay is being timed. It is delayed during entry and exit delay times. If a "Cross Zone" is not being timed it
will start a "Cross Zone" timer. If a "Cross Zone" is being timed it will create an instant alarm. This zone will automatically
bypass when enabled in Segment 1 of Location 23.

"13"

INSTANT ENTRY GUARD - This zone creates an instant alarm whenever it is tripped and the Stay LED is off. It will start
an entry delay time 2 if it is tripped and the system is armed and the Stay LED is on.

"14"

ENTRY/EXIT DELAY 1 WITH GROUP BYPASS ENABLED - A trip will start entry delay 1. This zone will bypass when
the "Group Bypass" command is entered at the keypad. The lack of a trip during exit delay will enable the Automatic
Bypass or Instant mode if so programmed.

"15"

INTERIOR FOLLOWER WITH GROUP BYPASS ENABLED - This zone will be instant when the system is armed and no
entry or exit delays are being timed. It is delayed during entry/exit delay times. This zone will bypass when the "Group
Bypass" command is entered at the keypad. This zone will automatically bypass if enabled in Segment 1 of Location 23.

"16"

INSTANT WITH GROUP BYPASS ENABLED - This zone creates an instant alarm whenever it is tripped and the Armed
LED is on. This zone will bypass when the "Group Bypass" command is entered at the keypad.

"17"

ENTRY/EXIT DELAY 1 WITH TAMPER ENABLED- A trip will start entry delay 1. The lack of a trip during exit delay will
enable the Automatic Bypass or Instant mode if so programmed. This configuration group can be used to enable
tamper on a wireless transmitter.

"18"

INTERIOR FOLLOWER WITH TAMPER AND AUTO-BYPASS ENABLED - This zone will be instant when the system is
armed and no entry or exit delay is being timed. It is delayed during entry and exit delay times. This zone will
automatically bypass if enabled in Segment 1 of Location 23. This configuration group can be used to enable tamper
on a wireless transmitter.

"19"

INSTANT WITH TAMPER ENABLED - This zone creates an instant alarm whenever it is tripped and the Armed LED is on.
This configuration group can be used to enable tamper on a wireless transmitter.

"20"

ENTRY/EXIT DELAY 2 WITH TAMPER ENABLED-A trip will start entry delay 2. The lack of a trip during exit delay will
enable the Automatic Bypass or Instant mode if so programmed. This configuration group can be used to enable
tamper on a wireless transmitter.