Appendix B: Reporting codes

90

NX-8E Control Panel Installation Manual

Loc. Description

Default

Setting

Segment 1

1 = Quick arm

2 = Re-exit

3 = Auto bypass

4 = Silent panic

5 = Audible panic

6 = Auxiliary 1

7 = Auxiliary 2

8 = Multi-keypress tamper

Segment 2

1 = LED extinguish enable

2 = Require user code by bypassing zones

3 = Bypass sounder alert

4 = AC pow er/low battery sounder alert

5 = Enable bypass toggle

6 = Enable silent auto arm

7 = Enable auto instant

8 = Reserved

Segment 3

1 = Open/close

2 = Bypass

3 = Restore

4 = Trouble

5 = Tamper

6 = Cancel

7 = Recent closing

8 = Exit error

Segment 4

1 = Late to close/early to open

2 to 8 = Reserved

Segment 5 = Reserved

109

Partition 8 entry and exit times

Segment 1 = Entry time 1

0

Segment 2 = Exit time 1

0

Segment 3 = Entry time 2

0

Segment 3 = Exit time 2

0

Segments 5 and 6 = Reserved

110

Zone type 1 alarm event code

8

111

Zone type 1 feature select

Segment 1

1 = Fire (enable for fire zone)

2 = 24-hour (enable for non-fire 24-hour)

3 = Keysw itch zone

4 = Follow er (enable for burg zones that are instant

during non-entry times)

5 = Delay 1 zone (enable to follow timer 1 entry/exit

times)

6 = Delay 2 zone (enable to follow timer 2 entry/exit

times)

7 = Interior (enable for auto bypass or stay arming

8 = Local only (enable if zone is not to be reported)

Segment 2

1 = Keypad audible on alarm

2 = Yelping siren on alarm

3 = Temporal siren on alarm

4 = Chime

5 = Bypassable

6 = Group shunt

7 = Force armable

8 = Entry guard