Step 9 — install external condensate trap and line – Carrier 50TCQA User Manual

Page 10

Advertising
background image

10

Economizer Hood and Two--Position Hood —
NOTE
: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for

use in the power exhaust hood assembly.

1. The indoor coil access panel will be used as the top of

the hood. Remove the screws along the sides and bot-

tom of the indoor coil access panel. See Fig. 10.

SIDE

PANEL

INDOOR

COIL

ACCESS

PANEL

INDOOR

COIL

ACCESS

PANEL

CAULK

HERE

TOP

SIDE

PANEL

C06025

Fig. 10 -- Indoor Coil Access Panel Relocation

2. Swing out indoor coil access panel and insert the

hood sides under the panel (hood top). Use the screws

provided to attach the hood sides to the hood top. Use

screws provided to attach the hood sides to the unit.

See Fig. 11.

B

TOP

PANEL

INDOOR COIL

ACCESS PANEL

19 1/16”

SCREW

HOOD DIVIDER

LEFT

HOOD

SIDE

33 3/8”

(848mm)

(483mm)

C06026

Fig. 11 -- Economizer Hood Construction

3. Remove the shipping tape holding the economizer ba-

rometric relief damper in place.

4. Insert the hood divider between the hood sides. See

Fig. 11 and 12. Secure hood divider with 2 screws on

each hood side. The hood divider is also used as the

bottom filter rack for the aluminum filter.

5. Open the filter clips which are located underneath the

hood top. Insert the aluminum filter into the bottom

filter rack (hood divider). Push the filter into position

past the open filter clips. Close the filter clips to lock

the filter into place. See Fig. 12.

DIVIDER

BAROMETRIC

RELIEF

CLEANABLE

ALUMINUM

FILTER

FILTER

HOOD

FILTER

CLIP

OUTSIDE

AIR

C08634

Fig. 12 -- Economizer Filter Installation

6. Caulk the ends of the joint between the unit top panel

and the hood top.

7. Replace the filter access panel.

Step 9 — Install External Condensate Trap and

Line

The unit has one

3

/

4

-in. condensate drain connection on

the end of the condensate pan and an alternate connection

on the bottom. See Fig. 13. Unit airflow configuration

does not determine which drain connection to use. Either

drain connection can be used with vertical or horizontal

applications.

When using the standard side drain connection, ensure the

red plug in the alternate bottom connection is tight. Do

this before setting the unit in place. The red drain pan can

be tightened with a

1

/

2

--in. square socket drive extension.

To use the alternate bottom drain connection, remove the

red drain plug from the bottom connection (use a

1

/

2

--in.

square socket drive extension) and install it in the side

drain connection.

DRAIN

(FACTORY-INSTALLED)

PLUG

CONDENSATE PAN (SIDE VIEW)

STANDARD

SIDE DRAIN

ALTERNATE

BOTTOM DRAIN

C08021

Fig. 13 -- Condensate Drain Pan (Side View)

The piping for the condensate drain and external trap can

be completed after the unit is in place. See Fig. 14.