PremierLinkt (Factory--Option) —

C08199

Fig. 28 -- PremierLink Controller

The PremierLink controller (see Fig. 28) is compatible

with Carrier Comfort Networkr (CCN) devices. This

control is designed to allow users the access and ability to

change factory--defined settings, thus expanding the

function of the standard unit control board. CCN service

access tools include System Pilot (TM), Touch Pilot (TM)

and Service Tool. (Standard tier display tools Navigatort

and Scrolling Marquee are not suitable for use with latest

PremierLink controller (Version 2.x).)

The PremierLink control is factory--mounted in the

50TCQ unit’s main control box to the left of the Central

Terminal Board (CTB). Factory wiring is completed

through harnesses connected to the CTB thermostat. Field

connections are made at a 16--pole terminal block (TB1)

located on the bottom shelf of the unit control box in front

of the PremierLink controller. The factory--installed

PremierLink control includes the supply--air temperature

(SAT) sensor. The outdoor air temperature (OAT) sensor is

included in the FIOP/accessory EconoMi$ert2 package.

The PremierLink controller requires the use of a Carrier

electronic thermostat or a CCN connection for time

broadcast to initiate its internal timeclock. This is

necessary for broadcast of time of day functions

(occupied/unoccupied).
NOTE:

PremierLink controller is shipped in Sensor

mode. To be used with a thermostat, the PremierLink

controller must be configured to Thermostat mode. Refer
to PremierLink Configuration instructions for Operating
Mode.
Supply Air Temperature (SAT) Sensor — On

FIOP--equipped 50TCQ unit, the unit is supplied with a

supply--air temperature (SAT) sensor (33ZCSENSAT).

This sensor is a tubular probe type, approx 6--inches

(12.7 mm) in length. It is a nominal 10--k ohm thermistor.

The SAT is factory--wired. The SAT probe is wire--tied to

the supply--air opening (on the horizontal opening end) in

its shipping position. Remove the sensor for installation.

Re--position the sensor in the flange of the supply--air

opening or in the supply air duct (as required by local

codes). Drill or punch a

1

/

2

--in. hole in the flange or duct.

Use two field--supplied, self--drilling screws to secure the

sensor probe in a horizontal orientation. See Fig. 29.

SUPPLY AIR

RETURN AIR

SUPPLY AIR
TEMPERATURE
SENSOR

ROOF
CURB

C08200

Fig. 29 -- Typical Mounting Location for Supply Air

Temperature (SAT) Sensor on Small Rooftop Units

NOTE:

Refer to Form 33CS--58SI for complete

PremierLink configuration, operating sequences and

troubleshooting information. Have a copy of this manual
available at unit start--up.
NOTE: The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact

with any of the unit’s heater surfaces.