Outdoor Air Temperature (OAT) Sensor — The OAT is

factory--mounted

in

the

EconoMi$er2

(FIOP

or

accessory). It is a nominal 10k ohm thermistor attached to

an eyelet mounting ring.

EconoMi$er2 — The PremierLink control is used with

EconoMi$er2 (option or accessory) for outdoor air

management. The damper position is controlled directly

by the PremierLink control; EconoMi$er2 has no internal

logic device.

Outdoor air management functions can be enhanced with

field--installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors)
Space CO

2

sensor

Outdoor air CO

2

sensor

Refer to Table 3 for accessory part numbers.

Field connections — Field connections for accessory

sensor and input devices are made at the 16--pole terminal

block (TB1) located on the control box bottom shelf in

front of the PremierLink control (See Fig. 30). Some input

devices also require a 24--vac signal source; connect at

CTB terminal R at “THERMOSTAT” connection strip for

this signal source. See connections figures on following

pages for field connection locations (and for continued

connections at the PremierLink board inputs).

Table 4 provides a summary of field connections for units

equipped with Space Sensor. Table 5 provides a summary

of field connections for units equipped with Space

Thermostat.

Space Sensors -- The PremierLink controller is

factory--shipped configured for Space Sensor Mode. A

Carrier T--55 or T--56 space sensor must be used. T--55

space temperature sensor provides a signal of space

temperature to the PremierLink control. T--56 provides

same space temperature signal plus it allows for

adjustment of space temperature setpoints from the face of

the sensor by the occupants.

2

3

4

5

6

1

SW1

SEN

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

C08201

Fig. 31 -- T--55 Space Temperature Sensor Wiring

Connect T--55 -- See Fig. 31 for typical T--55 internal

connections. Connect the T--55 SEN terminals to TB1

terminals 1 and 3 (see Fig. 32).

SEN

J6-7

J6-6

1

3

TB1

PL

SEN

C08212

Fig. 32 -- PremierLink T--55 Sensor

Connect T--56 -- See Fig. 33 for T--56 internal

connections. Install a jumper between SEN and SET

terminals as illustrated. Connect T--56 terminals to TB1

terminals 1, 3 and 5 (see Fig. 34).

2

3

4

5

6

1

SW1

SEN

SET

Cool

Warm

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

JUMPER
TERMINALS
AS SHOWN

BLK
(T56)

C08202

Fig. 33 -- T--56 Internal Connections

SEN

J6-7

J6-6

1

3

TB1

PL

SEN

SET

Jumper

TB1

PL

J6-5

5

SET

C08213

Fig. 34 -- PremierLink T--56 Sensor

Connect Thermostat — A 7--wire thermostat connection

requires a 24--v power source and a common connection.

Use the R and C terminals on the CTB’s THERMOSTAT

connection strip for these. Connect the thermostat’s Y1,

Y2, W1, W2 and G terminals to PremierLink TB1 as

shown in Fig. 35.

If the 50TCQ unit is equipped with factory--installed

smoke detector(s), disconnect the factory BLU lead at

TB1--6 (Y2) before connecting the thermostat. Identify the

BLU lead originating at CTB--DDC--1; disconnect at

TB1--6 and tape off. Confirm that the second BLU lead at

TB1--6 remains connected to PremierLink J4--8.