At any baud (9600, 19200, 38400 baud), the number of

controllers is limited to 239 devices maximum. Bus length

may not exceed 4000 ft, with no more than 60 total

devices on any 1000--ft section. Optically isolated RS--485

repeaters are required every 1000 ft.
NOTE: Carrier device default is 9600 band.
COMMUNICATION BUS WIRE SPECIFICATIONS —

The CCN Communication Bus wiring is field--supplied

and field--installed. It consists of shielded 3--conductor

cable with drain (ground) wire. The cable selected must

be identical to the CCN Communication Bus wire used for

the entire network.

See Table 6 for recommended cable.

Table 6 – Recommended Cables

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

NOTE: Conductors and drain wire must be at least 20
AWG, stranded, and tinned copper. Individual conductors
must be insulated with PVC, PVC/nylon, vinyl, Teflon, or
polyethylene. An aluminum/polyester 100% foil shield

and an outer jacket of PVC, PVC/nylon, chrome vinyl, or
Teflon with a minimum operating temperature range of
--20_C to 60_C is required. Do not run communication
wire in the same conduit as or next to any AC voltage
wiring.
The communication bus shields must be tied together at

each system element. If the communication bus is entirely

within one building, the resulting continuous shield must

be connected to ground at only one single point. If the

communication bus cable exits from one building and

enters another building, the shields must be connected to

the grounds at a lightning suppressor in each building (one

point only).

Connecting CCN bus:
NOTE: When connecting the communication bus cable,
a color code system for the entire network is
recommended to simplify installation and checkout. See
Table 7 for the recommended color code.

Table 7 – Color Code Recommendations

SIGNAL TYPE

CCN BUS WIRE

COLOR

CCN PLUG PIN

NUMBER

+

Red

1

Ground

White

2

---

Black

3

Connect the CCN (+) lead (typically RED) to the unit’s

TB1--12 terminal. Connect the CCN (ground) lead

(typically WHT) to the unit’s TB1--14 terminal. Connect

the CCN (--) lead (typically BLK) to the unit’s TB1--16

terminal. See Fig. 46.

CCN Bus

J2-1

J2-2

GND (WHT)

12

14

TB1

J2-3

– (BLK)

16

TB1

TB1

PL

+ (RED)

C08276

Fig. 46 -- PremierLink CCN Bus Connections