29

The raceway provides the UL required clearance between

high-- and low--voltage wiring. Pass the control wires

through the hole provided in the corner post, then feed the

wires thorough the raceway to the RTU--MP. Connect to

the wires to the removable Phoenix connectors and then

reconnect the connectors to the board.

Space Temperature (SPT) Sensors

A field--supplied Carrier space temperature sensor is

required with the RTU--MP to monitor space temperature.

There are 3 sensors available for this application:

S

33ZCT55SPT, space temperature sensor with override
button

S

33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment

S

33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment

Use 20 gauge wire to connect the sensor to the controller.

The wire is suitable for distances of up to 500 ft. Use a

three--conductor shielded cable for the sensor and setpoint

adjustment connections. If the setpoint adjustment

(slidebar) is not required, then an unshielded, 18 or 20

gauge, two--conductor, twisted pair cable may be used.

Connect T--55 -- See Fig. 31 for typical T--55 internal

connections. Connect the T--55 SEN terminals to

RTU--MP J20--1 and J20--2. See Fig. 50.

SEN

SEN

J20-1

J20-2

C08460

Fig. 50 -- RTU--MP T--55 Sensor Connections

Connect T--56 -- See Fig. 33 for T--56 internal

connections. Install a jumper between SEN and SET

terminals as illustrated. Connect T--56 terminals to

RTU--MP J20--1, J20--2 and J20--3 per Fig. 51.

SEN

J20-1

J20-2

SEN

SET

Jumper

J20-3

SET

C08461

Fig. 51 -- RTU--MP T--56 Sensor Connections

Connect T--59 -- The T--59 space sensor requires a

separate, isolated power supply of 24 VAC. See Fig. 51

for internal connections at the T--59. Connect the SEN

terminal (BLU) to RTU--MP J20--1. Connect the COM

terminal (BRN) to J20--2. Connect the SET terminal (STO

or BLK) to J20--3.

OR

SET

SEN

OPB

COM- PWR+

BLU (SPT)

BLK (STO)

24 VAC

SENSOR

WIRING

POWER
WIRING

BRN (COM)

NOTE: Must use a separate isolated transformer.

C07132

Fig. 52 -- Space Temperature Sensor Typical Wiring

(33ZCT59SPT)

Economizer controls —

Outdoor Air Enthalpy Control (PNO HH57AC077) --

The enthalpy control (HH57AC077) is available as a

field--installed accessory to be used with the EconoMi$er2

damper system. The outdoor air enthalpy sensor is part of

the enthalpy control. (The separate field--installed

accessory return air enthalpy sensor (HH57AC078) is

required for differential enthalpy control. See “Return Air

Enthalpy Sensor” below.)

Locate the enthalpy control in the economizer hood.

Locate two GRA leads in the factory harness and connect

these leads to enthalpy control sensors 2 and 3. See

Fig. 36. Connect the enthalpy control power input

terminals to economizer actuator power leads RED

(connect to TR) and BLK (connect to TR1).

The outdoor enthalpy changeover setpoint is set at the

enthalpy controller.

Differential Enthalpy Control — Differential enthalpy

control is provided by sensing and comparing the outside

air and return air enthalpy conditions. Install the outdoor

air enthalpy control as described above. Add and install a

return air enthalpy sensor.

Return Air Enthalpy Sensor — Mount the return--air

enthalpy sensor (HH57AC078) in the return--air duct. The

return air sensor is wired to the enthalpy controller

(HH57AC077). See Fig. 37.

To wire the return air enthalpy sensor, perform the

following:

1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable

to connect the return air enthalpy sensor to the enthal-

py controller.

2. At the enthalpy control remove the factory--installed

resistor from the (SR) and (+) terminals.

3. Connect the field--supplied RED wire to (+) spade

connector on the return air enthalpy sensor and the

(SR+) terminal on the enthalpy controller. Connect

the BLK wire to (S) spade connector on the return air

50TC

Q

A