Fig. 25 -- Typical Module Installation

Single Point Boxes and Supplementary Fuses — When

the unit MOCP device value exceeds 60--A, unit--mounted

supplementary fuses are required for each heater circuit.

These fuses are included in accessory Single Point Boxes,

with power distribution and fuse blocks. The single point

box will be installed directly under the unit control box,

just to the left of the partition separating the indoor

section (with electric heaters) from the outdoor section.

The Single Point Box has a hinged access cover. See

Fig. 26. The Single Point Box also includes pigtails to

complete the wiring between the Single Point Box and the

unit’s main control box terminals. Refer to the accessory

heater and Single Point Box installation instructions for

details on tap connections.

ALLIED PA

MODEL NO.

ERIAL NO.

CORP.

11

13

21

23

OD

22.2

3

1

23

ISTED AIR

NDITIONING

UIP ACCESS
346N.

P / N

2-

5610-4

REV

1

1

13

2

1

2

3

CONTROL
BOX

BUSHING

SINGLE
POINT BOX
MOUNTING
SCREWS

FOAM
BUSHING

DRIP BOOT
BRACKET
MOUNTING
SCREWS

HEATER
RELAYS

POWER
WIRES

HEATER
MOUNTING
SCREWS

C08136

Fig. 26 -- Typical Single Point Installation

All fuses on 50TCQ units are 60--A. (Note that all heaters

are qualified for use with a 60--A fuse, regardless of actual

heater ampacity, so only 60--A fuses are necessary.)
Single Point Boxes without Fuses — Refer to accessory

heater and Single Point Box installation instructions for

details on tap connections.
Low--Voltage Control Connections — Run the

low--voltage control leads from the heater module(s) --

VIO and BRN (two of each if two modules are installed;

identify for Module #1) -- to the 4--pole terminal board

TB4 located on the heater bulkhead to the left of Heater

#1. Connect the VIO leads from Heater #1 and Heater #2

to terminal TB4--1. Connect the BRN leads to terminal

TB4--3. See Fig. 27.

DEFROST

BOARD

ORN

BRN

Field
Connections

E-HEAT

P3-3

1

3

ORN

BRN

VIO

BRN BRN

VIO

TB4

VIO

HR2

HR1

BRN

VIO

BRN

Elec Htr

HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)

C09013

Fig. 27 -- Accessory Electric Heater Control Connections