Step 11 — adjust factory--installed options – Carrier 50TCQA User Manual

Page 44

Advertising
background image

44

Legend and Notes for Table 10

LEGEND:

CO

--- Convenient outlet

DISC

--- Disconnect

FLA

--- Full load amps

IFM

--- Indoor fan motor

LRA

--- Locked rotor amps

MCA

--- Minimum circuit amps

MOCP

--- Maximum over current protection

PE

--- Power exhaust

UNPWR CO

--- Unpowered convenient outlet

NOTES:

1. In compliance with NEC requirements for multimotor and

combination load equipment (refer to NEC Articles 430 and

440), the overcurrent protective device for the unit shall be

fuse or HACR breaker. Canadian units may be fuse or circuit

breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply

voltage is greater than 2%. Use the following formula to de-

termine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the

maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than

2%, contact your local electric utility company immediately.

Economizer

2 Position Damper

Unit Without Economizer or
2 Position Damper

C08631

Fig. 65 -- EconoMi$ert IV Wiring

Step 11 — Adjust Factory--Installed Options

Smoke Detectors —

Smoke detector(s) will be connected at the Central

Terminal Board (CTB), at terminals marked “Smoke

Shutdown”. Remove jumper JMP 3 when ready to

energize unit.

EconoMi$er IV Occupancy Switch —

Refer to Fig. 65 for general EconoMi$er IV wiring.

External occupancy control is managed through a

connection on the Central Terminal Board.

If external occupancy control is desired, connect a time

clock or remotely controlled switch (closed for Occupied,

open for Unoccupied sequence) at terminals marked

OCCUPANCY on CTB. Remove or cut jumper JMP 2 to

complete the installation.

50TC

Q

A