Table 8 – RTU--MP Controller Inputs and Outputs

POINT NAME

BACnet OBJECT

NAME

TYPE OF I/O

CONNECTION PIN

NUMBERS

INPUTS

Space Temperature Sensor

sptsens

AI (10K Thermistor)

J20---1, 2

Supply Air Temperature

sat

AI (10K Thermistor)

J2---1, 2

Local Outside Air Temperature Sensor

oatsens

AI (10K Thermistor)

J2---3, 4

Space Temperature Offset Pot

sptopot

AI (100K Potentiometer)

J20---3

Indoor Air Quality

iaq

AI (4---20 ma)

J4---2, 3

Outdoor Air Quality

oaq

AI (4---20 ma)

J4---5, 6

Safety Chain Feedback

safety

DI (24 VAC)

J1---9

Compressor Safety

compstat

DI (24 VAC)

J1---2

Fire Shutdown

firedown

DI (24 VAC)

J1---10

Enthalpy Switch

enthalpy

DI (24 VAC)

J2---6, 7

Humidistat Input Status

humstat

DI (24 VAC)

J5---7, 8

CONFIGURABLE INPUTS*

Space Relative Humidity

sprh

AI (4---20 ma)

J4---2,3 or J4---5,6

Outside Air Relative Humidity

oarh

AI (4---20 ma)

Supply Fan Status

fanstat

DI (24 VAC)

J5---1,2 or J5---3,4 or

J5 5,6 or J5---7,8

Filter Status

filtstat

DI (24 VAC)

Remote Occupancy Input

remocc

DI (24 VAC)

OUTPUTS

Economizer Commanded Position

econocmd

4---20ma

J2---5

Supply Fan Relay State

sf

DO Relay (24VAC , 1A)

J1---4

Compressor 1 Relay State

comp_1

DO Relay (24VAC , 1A)

J1---8

Compressor 2 Relay State

comp_2

DO Relay (24VAC , 1A)

J1---7

Heat Stage 1 Relay State

heat_1

DO Relay (24VAC , 1A)

J1---6

Heat Stage 2 Relay State

heat_2

DO Relay (24VAC , 1A)

J1---5

Power Exhaust Relay State

aux_2

DO Relay (24VAC , 1A)

J11---3

Dehumidification Relay State

humizer

DO Relay (24VAC, 1A)

J11---7, 8

LEGEND

AI --- Analog Input

AO --- Analog Output

DI --- Discrete Input

DO --- Discrete Output

* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.

The RTU--MP controller requires the use of a Carrier

space sensor. A standard thermostat cannot be used with

the RTU--MP system.

Supply

Air

Temperature

(SAT)

Sensor

--

On

FIOP--equipped 50TCQ unit, the unit is supplied with a

supply--air temperature (SAT) sensor (33ZCSENSAT).

This sensor is a tubular probe type, approx 6--inches (12.7

mm) in length. It is a nominal 10--k ohm thermistor.

The SAT is factory--wired. The SAT probe is wire--tied to

the supply--air opening (on the horizontal opening end) in

its shipping position. Remove the sensor for installation.

Re--position the sensor in the flange of the supply--air

opening or in the supply air duct (as required by local

codes). Drill or punch a

1

/

2

--in. hole in the flange or duct.

Use two field--supplied, self--drilling screws to secure the

sensor probe in a horizontal orientation. See Fig. 29.

Outdoor Air Temperature (OAT) Sensor -- The OAT is

factory--mounted

in

the

EconoMi$er2

(FIOP

or

accessory). It is a nominal 10k ohm thermistor attached to

an eyelet mounting ring.

EconoMi$er2 -- The RTU--MP control is used with

EconoMi$er2 (option or accessory) for outdoor air

management. The damper position is controlled directly

by the RTU--MP control; EconoMi$er2 has no internal

logic device.

Outdoor air management functions can be enhanced with

field--installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors)
Space CO

2

sensor

Outdoor air CO

2

sensor

Field Connections -- Field connections for accessory

sensors and input devices are made the RTU--MP, at plugs

J1, J2, J4, J5, J11 and J20. All field control wiring that

connects to the RTU--MP must be routed through the

raceway built into the corner post as shown in Fig. 22.