Carrier 50TCQA User Manual

Page 21

Advertising
background image

21

Table 4 – Space Sensor Mode

TB1 TERMINAL

FIELD CONNECTION

INPUT SIGNAL

1

T55---SEN/T56---SEN

Analog (10k thermistor)

2

RMTOCC

Discrete, 24VAC

3

T55---SEN/T56---SEN

Analog (10k thermistor)

4

CMPSAFE

Discrete, 24VAC

5

T56---SET

Analog (10k thermistor)

6

FSD

Discrete, 24VAC

7

LOOP---PWR

Analog, 24VDC

8

SPS

Discrete, 24VAC

9

IAQ---SEN

Analog, 4---20mA

10

FILTER

Discrete, 24VAC

11

IAQ---COM/OAQ---COM/RH---COM

Analog, 4---20mA

12

CCN + (RED)

Digital, , 5VDC

13

OAQ---SEN/RH---SEN

Analog, 4---20mA

14

CCN Gnd (WHT)

Digital, 5VDC

15

AUX OUT(Power Exhaust)

(Output)Discrete 24VAC

16

CCN --- (BLK)

Digital, 5VDC

LEGEND:

T55

--- Space Temperature Sensor

FSD --- Fire Shutdown

T56

--- Space Temperature Sensor

IAQ --- Indoor Air Quality (CO

2

)

CCN

--- Carrier Comfort Network (communication bus)

OAQ --- Outdoor Air Quality (CO

2

)

CMPSAFE

--- Compressor Safety

RH --- Relative Humidity

FILTER

--- Dirty Filter Switch

SFS --- Supply Fan Status

Table 5 – Thermostat Mode

TB1 TERMINAL

FIELD CONNECTION

INPUT SIGNAL

1

RAT SEN

Analog (10k thermistor)

2

G

Discrete, 24VAC

3

RAT SEN

Analog (10k thermistor)

4

Y1

Discrete, 24VAC

5
6

Y2

Discrete, 24VAC

7

LOOP---PWR

Analog, 24VDC

8

W1

Discrete, 24VAC

9

IAQ---SEN

Analog, 4---20mA

10

W2

Discrete, 24VAC

11

IAQ---COM/OAQ---COM/RH---COM

Analog, 4---20mA

12

CCN + (RED)

Digital, 5VDC

13

OAQ---SEN/RH---SEN

Analog, 4---20mA

14

CCN Gnd (WHT)

Digital, 5VDC

15

AUX OUT (Power Exhaust)

(Output) Discrete 24VAC

16

CCN --- (BLK)

Digital, 5VDC

LEGEND:
CCN

---

Carrier Comfort Network (communication bus)

RH --- Relative Humidity

G

---

Thermostat Fan

W1 --- Thermostat Heat Stage 1

IAQ

---

Indoor Air Quality (CO

2

)

W2 --- Thermostat Heat Stage 2

OAQ

---

Outdoor Air Quality (CO

2

)

Y1 --- Thermostat Cool Stage 1

RAT

---

Return Air Temperature

Y2 --- Thermostat Cool Stage 2

50TC

Q

A

Advertising