Carrier 50TCQA User Manual

Page 14

Advertising
background image

14

LOW VOLTAGE

CONDUIT

CONNECTOR

HIGH VOLTAGE

CONDUIT

CONNECTOR

C08637

Fig. 20 -- Thru--Base Connection Fittings

Field--supplied and field--installed liquidtight conduit

connectors and conduit may be attached to the connectors

on the basepan. Pull correctly rated high voltage and low

voltage through appropriate conduits. Connect the power

conduit to the internal disconnect (if unit is so equipped)

or to the external disconnect (through unit side panel). A

hole must be field cut in the main control box bottom on

the left side so the 24--v control connections can be made.

Connect the control power conduit to the unit control box

at this hole.

Units without Thru--Base Connections —

1. Install power wiring conduit through side panel open-

ings. Install conduit between disconnect and control

box.

2. Install power lines to terminal connections as shown

in Fig. 16.

All Units —

Voltage to compressor terminals during operation must be

within voltage range indicated on unit nameplate. See

Table 10. On 3--phase units, voltages between phases must

be balanced within 2% and the current within 10%. Use

the formula shown in the legend for Table 10, Note 2 (see

page 44) to determine the percent of voltage imbalance.

Operation on improper line voltage or excessive phase

imbalance constitutes abuse and may cause damage to

electrical components. Such operation would invalidate

any applicable Carrier warranty.

Field Control Wiring —

The 50TCQA unit requires an external temperature

control device. This device can be a thermostat

(field--supplied) or a PremierLink controller (available as

factory--installed option or as field--installed accessory, for

use on a Carrier Comfort Network or as a stand alone

control) or the RTU--MP Controller for Building

Management

Systems

using

non--CCN

protocols

(RTU--MP is available as a factory--installed option only).

Thermostat —

Install

a

Carrier--approved

accessory

2

stage

Cooling/Heating thermostat according to installation

instructions included with the accessory. The 50TCQ

models do not require a thermostat with an O function to

control the reversing valve operation. If using an

electronic thermostat, configure it for “non--heat pump”

operation. Locate the thermostat accessory on a solid wall

in the conditioned space to sense average temperature in

accordance with the thermostat installation instructions.

If the thermostat contains a logic circuit requiring 24--v

power, use a thermostat cable or equivalent single leads of

different colors with minimum of seven leads. If the

thermostat does not require a 24--v source (no “C”

connection required), use a thermostat cable or equivalent

with minimum of six leads. Check the thermostat

installation instructions for additional features which

might require additional conductors in the cable.

For wire runs up to 50 ft. (15 m), use no. 18 AWG

(American Wire Gage) insulated wire (35_C minimum).

For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated

wire (35_C minimum). For over 75 ft. (23 m), use no. 14

AWG insulated wire (35_C minimum). All wire sizes

larger than no. 18 AWG cannot be directly connected to

the thermostat and will require a junction box and splice

at the thermostat.

X

C

G

W2

C

W2

G

W1

O/B/Y2

Y2

R

W1

R

Y1

Y1

T
H
E
R
M
O
S
T
A
T

(Note 1)

(Note 2)

Note 1: Typical multi-function marking. Follow manufacturer’s configuration

instructions to select Y2. Do not configure for O output.

Note 2: W2 connection not required on units without electric heating.

Field Wiring

Central

Terminal

Board

Typical

Thermostat

Connections

C09012

Fig. 21 -- Typical Low--Voltage Control Connections

Unit without thru--base connection kit —

Pass the thermostat control wires through the hole

provided in the corner post; then feed the wires through

the raceway built into the corner post to the control box.

Pull the wires over to the terminal strip on the upper--left

corner of the Central Terminal Board (CTB). See Fig. 22.
NOTE:

If thru--the--bottom connections accessory is

used, refer to the accessory installation instructions for
information on routing power and control wiring.
Heat Anticipator Settings —

Set heat anticipator settings at 0.14 amp for the first stage

and 0.14 amp for second--stage heating, when available.

50TC

Q

A

Advertising