Carrier 50TCQA User Manual

Page 32

Advertising
background image

32

Local Access

BACview

6

Handheld

The BACview

6

is a keypad/display interface used to

connect to the RTU--MP to access the control information,

read sensor values, and test the RTU, see Fig. 57. This is

an accessory interface that does not come with the MP

controller and can only be used at the unit. Connect the

BACview

6

to the RTU--MP’s J12 local access port. There

are 2 password protected levels in the display (User and

Admin). The user password is defaulted to 0000 but can

be changed. The Admin password is 1111 and cannot be

changed. There is a 10 minute auto logout if a screen is

idle. See Form 48--50H--T--2T, Appendix A for navigation

and screen content.

Virtual BACview

Virtual BACview is a freeware computer program that

functions as the BACview

6

Handheld. The USB Link

interface (USB--L) is required to connect a computer to

the RTU--MP board. The link cable connects a USB port

to the J12 local access port. This program functions and

operates identical to the handheld.

RTU--MP Troubleshooting

Communication LEDs

The LEDs indicate if the controller is speaking to the

devices on the network. The LEDs should reflect

communication traffic based on the baud rate set. The

higher the baud rate the more solid the LEDs will appear.

C07170

Fig. 57 -- BACview

6

Handheld Connections

50TC

Q

A

Advertising