6.2 DIP Switches


There are three DIP switches on the control board. The usage of each switch is as tabulated:

SW1

8-way

To set the Device ID

SW2

4-way

To set the baud rate and communication type

SW3

8-way

To set the type of serial communication (i.e.
whether RS232, 422 or 485)


The following tables show the settings for each of the three DIP switches.
Note that a "-"indicates an "OFF" position.

Table 1: SW1 (Device ID)


SW1 is used to set the Device ID of the device. It has a row of 8 DIP switches. The range of Device IDs that
can be set is 0 to 255. However, the acceptable range for field operation is 1 to 254. The Device ID is set
according to the binary format of an 8-bit byte. An "ON" position is interpreted as binary bit 0. To help you
to find the dip switching settings for a particular Device ID, use the index value associated with each bit.

Switch /
Device ID

1

2

3

4

5

6

7

8

Index Value

1

2

4

8

16

32

64

128

0

(Not

used) ON ON ON ON ON ON ON ON

1

-

ON

ON

ON

ON

ON

ON

ON

2

ON - ON

ON

ON

ON

ON

ON

3

-

-

ON

ON

ON

ON

ON

ON

4

ON

ON - ON

ON

ON

ON

ON

5

-

ON

-

ON

ON

ON

ON

ON

6

ON - - ON

ON

ON

ON

ON

7

-

-

-

ON

ON

ON

ON

ON

8

ON ON ON - ON ON ON ON

9

-

ON

ON

-

ON

ON

ON

ON

10

ON - ON - ON

ON

ON

ON

:
:
:

:
:
:

:
:
:

253

- ON - - - - - -

254

ON

-

-

-

-

-

-

-

255

(Not

used) - - - - - - - -


Examples:
Switch/
Device ID

1 2 3 4 5 6 7 8

Index

Value

1 2 4 8 16 32 64 128

Device

ID

5 = 1 + 4

Position

- ON - ON ON ON ON ON

Device

ID

6 = 2 +

4

Position

ON - - ON ON ON ON ON

Device ID 10

=

2

+

8

Position ON - ON

- ON

ON

ON

ON

Device

ID

30 =

2 +

4 +

8 +

16

Position ON - - - -

ON

ON

ON