Table 3 — Maximum Gas Flow Capacity*

NOMINAL

IRON PIPE,

SIZE

(In.)

INTERNAL

DIAMETER

(In.)

LENGTH OF PIPE, FTf

10

20

30

40

50

60

70

80

90

100

125

150

175

200

V2

.622

175

120

97

82

73

66

61

57

53

50

44

40

%

.824

360

250

200

170

151

138

125

118

110

103

93

84

77

72

1

1 049

680

465

375

320

285

260

240

220

205

195

175

160

145

135

1V4

1.380

1400

950

770

600

580

530

490

460

430

400

360

325

300

280

IV

2

1.610

2100

1460

1180

990

900

810

750

690

650

620

550

500

460

430

‘Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or iess. Pressure drop of 0 5-in. wg

(based on a 0.60 specific gravity gas). Ref: Tabie C-4, Nationai Fire Protection Association NFPA54.

fThis iength inciudes an ordinary number of fittings.