Carrier 48SX024-048 User Manual

Page 38

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 13 — Dry-Coil Air Delivery* — Downflow Discharge at 230 and 460 V — Unit 48SX

(Deduct 10% from Cfm and Watts for 208 V Operation)

UNIT

48SX

MOTOR

SPEED

AIR

DELIVERY

EXTERNAL STATIC PRESSURE (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024,
030

Low

Watts

280

275

265

255

250

245

240

t

t

t

t

Cfm

820

810

755

700

660

600

560

t

t

t

t

Med

Watts

365

360

350

345

340

330

320

310

300

t

t

Cfm

1025

1010

975

940

900

850

800

720

630

t

t

High

Watts

t

t

490

480

470

460

445

430

410

390

380

Cfm

t

t

1300

1255

1200

1150

1080

1005

915

790

620

036

Low

Watts

520

495

474

458

445

425

t

t

t

t

t

Cfm

1375

1335

1290

1240

1200

1140

t

t

t

t

t

Med

Watts

575

560

535

510

480

460

440

425

t

t

t

Cfm

1520

1490

1450

1400

1380

1300

1200

1080

t

t

t

High

Watts

t

t

t

t

650

614

575

540

510

480

t

Cfm

t

t

t

t

1560

1500

1380

1280

1170

1060

t

042

Low

Watts

490

480

470

460

450

430

410

390

t

t

t

Cfm

1400

1380

1340

1300

1250

1200

1140

1070

t

t

t

Med

Watts

590

580

560

545

525

505

480

450

420

t

t

Cfm

1600

1560

1540

1470

1430

1360

1300

1220

1120

t

t

High

Watts

t

t

t

t

t

700

670

640

600

560

500

Cfm

t

t

t

t

t

1780

1670

1600

1480

1340

1100

048

Low

Watts

1050

1000

970

930

870

810

750

680

600

t

t

Cfm

1850

1830

1800

1785

1750

1700

1640

1500

1330

t

t

High

Watts

t

t

t

1050

1000

930

870

810

740

665

t

Cfm

t

t

t

2000

1940

1850

1750

1635

1500

1300

t

*Air delivery values are without air filter and are for dry coil See Table 14 for wet coil pressure drop. Deduct field-supplied air filter pressure drop

and wet coil pressure drop to obtain external static pressure available for ducting.

tUnit air delivery is outside of operating range.
NOTE; Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity Evaporator-coil icing
may occur at airflows below this point. Water blow-off may occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.

Table 14 — Wet Coil Pressure Drop

UNIT SIZE

AIRFLOW

(cfm)

PRESSURE DROP

(in. wg)

600

0.069

018*

700

0 082

800

0102

900

0116

600

0.039

024

700

0.058

800

0.075

900

0.088

900

0.088

030

1000

0.095

1200

0.123

1000

0.068

036

1200

0.088

1400

0.108

1600

0123

1000 ■;

0 048

042

1200

0.069

1400

0.088

1600

0.102

1400

0.068

048

1600

0.075

1800

0.088

1700

0.082

060*

1900

0.095

2100

0.108

2300

0.123

‘Unit 48SS only.

t

38