Table 9 — Required Suction-Tube Temperature (F)*

TEMP (F)

61.5

64.2

67.1

70.0

73.0

76.0

79.2

82.4

85.7

0

35

37

39

41

43

45

47

49

51

2

37

39

41

43

45

47

49

51

53

4

39

41

43

45

47

49

51

53

55

6

41

43

45

47

49

51

53

55

57

8

43

45

47

49

51

53

55

57

59

10

45

47

49

51

53

55

57

59

61

12

47

49

51

53

55

57

59

61

63

14

49

51

53

55

57

59

61

63

65

16

51

53

55

57

59

61

63

65

67

18

53

55

57

59

61

63

65

67

69

20

55

57

59

61

63

65

67

69

71

22

57

59

61

63

65

67

69

71

73

24

59

61

63

65

67

69

71

73

75

26

61

63

65

67

69

71

73

75

77

28

63

65

67

69

71

73

75

77

79

30

65

67

69

71

73

75

77

79

81

32

67

69

71

73

75

77

79

81

83

34

69

71

73

75

77

79

81

83

85

36

71

73

75

77

79

81

83

85

87

38

73

75

77

79

81

83

85

87

89

40

75

77

79

81

83

85

87

89

91

‘Temperature at suction service vaive

Table 10 — Dry-Coil Air Delivery* — Horizontal Discharge at 230 and 460 V - Unit 48SS

(Deduct 10% from Cfm and Watts for 208 V Operation)

UNIT

48SS

MOTOR

SPEED

AIR

DELIVERY

EXTERNAL STATIC PRESSURE (In. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

018

Low

Watts

230

225

220

210

195

170

t

t

t

t

t

Cfm

760

745

725

695

640

540

t

t

t

t

t

High

Watts

t

t

t

t

270

235

200

t

t

t

t

Cfm

t

t

t

t

850

700

450

t

t

t

t

024,

030

Low

Watts

275

275

273

269

260

257

249

t

t

t

t

Cfm

857

835

802

782

745

717

663

t

t

t

t

Med

Watts

371

368

360

349

345

326

319

304

293

t

t

Cfm

1079

1063

1027

996

978

919

865

783

726

t

t

High

Watts

514

493

476

460

443

425

401

378

344

t

t

Cfm

1409

1383

1324

1282

1223

1156

1068

984

857

t

t

036

Low

Watts

473

447

427

418

395

367

346

337

323

t

t

Cfm

1253

1253

1172

1130

1047

946

865

829

768

t

t

Med

Watts

519

500

478

459

439

410

377

357

340

t

t

Cfm

1414

1366

1287

1234

1162

1074

920

829

743

t

t

High

Watts

667

634

609

593

564

541

506

469

436

422

t

Cfm

1734

1639

1563

1461

1370

1292

1157

960

829

743

t

042

Low

Watts

678

635

604

580

550

520

493

455

430

t

t

Cfm

1540

1515

1475

1430

1375

1280

1225

1128

1020

t

t

High

Watts

t

820

785

750

700

680

649

612

570

t

t

Cfm

t

1825

1750

1685

1610

1525

1485

1355

1215

t

t

048

Low

Watts

t

t

854

786

744

706

641

606

557

511

t

Cfm

t

t

. 2026

1905

1830

1752

1603

1513

1367

1228

t

High

Watts

t

t

t

905

846

824

804

748

683

637

t

Cfm

t

t

t

2025

1905

1830

1752

1603

1398

1228

t

060

Low

Watts

1000

991

970

925

904

875

849

830

819

t

t

Cfm

2125

2110

2085

2040

2009

1960

1900

1845

1775

t

t

Med

Watts

1355

1315

1265

1212

1158

1103

1045

987

925

880

t

Cfm

2480

2440

2388

2330

2266

2198

2125

2050

1968

1890

t

High

Watts

t

t

1435

1375

1310

1265

1175

1108

1010

915

t

Cfm

t

t

2509

2450

2386

2310

2235

2160

2083

1888

t

‘Air deiivery values are without air filter and are for dry coil. See Table 14 for wet coil pressure drop. Deduct field-supplied air filter pressure drop

and wet coil pressure drop to obtain external static pressure available for ducting.

tUnit air delivery is outside of operating range.

NOTE; Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-coil icing
may occur at airflows below this point. Water blow-off may occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.