o 15/16=^

1 9/16'

(23.8)„

(39.7)^

B

S2 49 g/16'

(1320.8) (1259.3)

OPTIONAL RETURN

AIR OPENING

13/16'

(46 2)

OPTIONAL SUPPLY
AIR OPENING

RIGHT SIDE VIEW

ACCESS PANEL

1

\ / 4

C31.75)

ALTERNATE POWER ENTRY

EVAP COIL ACCESS

0 7/0

(22.23)\

ALTERNATE LV ENTRY

_-3

5/16'

'^(BA.I)

REQ’D CLEARANCES FOR SERVICING in. (mm)

Duct panel .

.

...

.

. 0

Unit top

. .

36(914)

Side opposite ducts

...

36(914)

Compressor access

36(914)

(Except for NEC requirements)

REQ’D CLEARANCES TO COMBUSTIBLE MATL. in (mm)

~

4Í7l219)

14 (356)

........................0

. . 9 (229)

. . 0

. .

30 (762)

10 1/16

(450 0)

5 5/0

(142.9)t

1 3/16-

(20

6

)

— 10 -I

(253.0)

-11 1/21

(292.1)

13 1/2'

(342.9)

11 'S/16'

■ (207.31.4

f

12 13/16'.

LEFT SIDE VIEW

1 3/8'-

(34.9)

CG
COND

LV
MAT’L

NEC
REQ’D

Maximum extension of overhangs
Unit top.......................
Duct side of unit .
Side opposite ducts
Bottom of unit
Flue panel

LEGEND

— Center of Gravity
— Condenser
— Low Voltage
— Material
— National Electrical Code
— Required

COMPRESSOR ACCESS PANEL

37 7/16"

(950 9)

UNIT

ELECTRICAL

CHARACTERI8TIC8

UNIT WEIGHT

CORNER WEIGHT

(Ib/kg)

lb

kg

A

B

C

D

488X042060,080

208/230-1-60, 208/230-3-60, 460-3-60

415

189

106/48

97/44

126/57 86/39

488X042100,120

208/230-1-60, 208/230-3-60, 460-3-60

427

194

109/50 100/45 129/59 89/40

488X048080

208/230-1-60, 208/230-3-60, 460-3-60

446

293

115/52

91/41

164/75 76/35

488X048100/120/140

208/230-1-60, 208/230-3-60, 460-3-60

458

208

118/54

94/43

167/76 79/36

W

UNIT

CENTER OF GRAVITY (in./mm)

X

Y

Z

488X042060,080

26.55/674 4

21 22/539 0

17 66/448.6

488X042100,120

26.50/673.0

21.24/539.6

17.66/448.6

48SX048080

28.25/717 6

20 04/509 0

17.66/448.6

488X048100/120/140

28.16/715.3

20 08/510 0

17.66/448 6

NOTE: Ciearances must be maintained to prevent recirculation of
air from outdoor-fan discharge

NEC REQ’D CLEARANCES, in (mm)

Between units, control box side
Unit and ungrounded surfaces, control box side
Unit and block or concrete walls and other grounded
surfaces, control box side

42 (1067)

36 (914)

42 (1067)

Fig. 9 — 488X042,048 With Optional Base Rail, Unit Dimensions