Table 7e — superheat charging table, 48ss042 – Carrier 48SX024-048 User Manual

Page 33

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 7D — Superheat Charging Table, 48SS036

#

TEMP (F)

AIR ENT

EVAP AIR - CFM

1200

Evap Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

8 4

8 . 4

8 4

8 4

12.5

16.7

18.7

20.7

22.0

23.4

24.8

26.1

70

SPH

50

5.0

5.0

5.0

90

13.1

15.9

186

20.0

21.3

22 7

24.0

75

SPH

*

*

*

*

5.4

9.6

13 1

166

17.9

19.3

20 6

22.0

80

SPH

*

*

*

*

6.0

103

14.5

15.9

17.3

18.6

20 0

85

SPH

*

*

*

*

*

*

75

125

13.9

15.2

16.5

179

90

SPH

*

*

*

*

*

*

5.4

10.4

12.5

146

168

18.8

95

SPH

*

*

*

*

*

*

*

8.4

11.3

14 1

17.0

19.8

100

SPH

*

*

*

*

*

*

*

6.4

10 0

135

17.1

20.7

105

SPH

*

*

*

*

*

*

*

*

8.7

13.0

17.3

21 7

110

SPH

*

*

*

*

*

•*

*

*

9.3

12.4

15.6

187

115

SPH

*

*

*

*

*

*

*

*

100

11.9

13.8

158

Ewb
SPH

LEGEND

— Entering Wet Bulb
— Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrig­

erant slugging may occur

Table 7E — Superheat Charging Table, 48SS042

TEMP (F)

EVAP AIR - CFM

1400

COND

Evap Air Ewb (F

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

27.2

27.2

27.2

28.9

30.5

32.2

32.5

32.9

33.2

33 2

33 2

33.2

70

SPH

25 1

25.1

25.1

26.8

28.5

30.1

30.8

31 5

32.2

32.0

31.9

31.7

75

SPH

23 1

23.1

23.1

24.8

26.4

28 1

29.1

30 2

31.2

30.9

30 6

30.3

80

SPH

22.5

22.5

22.5

23.7

24.9

26 0

27 4

28.8

30.2

30.0

29 8

29.5

85

SPH

22 0

22.0

22.0

22.7

23.3

24.0

25.7

27.5

29 2

29.1

28.9

28 8

90

SPH

21.5

21.5

21.5

22.1

22.8

23.4

25 0

26.6

28.2

28 2

28 1

28.1

95

SPH

20.9

20 9

20.9

21.6

22.2

22.9

24 3

25.8

27.2

27.3

27 3

27.3

100

SPH

20.3

20 3

20.3

21 0

21.7

22.3

23 6

24.9

26 2

26 3

26 5

26.6

105

SPH

19.8

19.8

19.8

20 5

21.1

21.8

22.9

24.1

25 2

25.4

25 6

25.9

110

SPH

17.8

17.8

178

18.4

19.1

19.7

21.2

22.7

24.2

24 6

24 9

25.3

115

SPH

15.7

15.7

157

164

170

17.7

19.5

21.4

23 2

23 7

24.2

24.8

#

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

Table 7F — Superheat Charging Table, 48SS048

TEMP (F)

EVAP AIR - CFM

1600

COND

Evap Air — Ewb (F

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

190

19.0

19.0

19.0

21.7

24 3

26.0

27.7

27.9

28 2

28.4

28.6

70

SPH

15.4

15.4

15.4

15.4

18.1

20.8

22 5

24.1

25.1

26.1

27.1

28.1

75

SPH

11.9

11.9

11.9

11.9

14.6

17.2

18.9

20.6

22.3

24.0

25.8

27 5

80

SPH

8.4

8.4

8.4

8.4

11.0

137

15.4

17.0

19.5

22 0

24.5

27.0

85

SPH

5.0

50

5.0

5.0

7.5

10.1

11.8

13.5

16.7

20 0

23.2

26 4

90

SPH

*

*

*

*

*

66

9.0

11.4

14.7

17.9

21.1

24.4

95

SPH

*

*

*

*

*

*

6.2

9.4

12.6

15.9

19 1

22.3

100

SPH

*

*

*

*

*

*

*

7.3

106

13.8

17.0

20 3

105

SPH

*

*

*

*

*

*

*

53

8.5

11 8

15.0

18.2

110

SPH

*

*

*

*

*

*

*

69

11.2

155

19.8

115

SPH

*

•*

*

*

*

*

*

*

5.3

10.6

160

21.3

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrig­

erant slugging may occur.

33