OPTIONAL RETURN
AIR OPENING

1 1/4' 01.0) DIA

ALTERNATE POWER ENTRY

8 l/4'-<

(203.6)

13/16'

(46 2)

OPTIONAL SUPPLY
AIR OPENING

-4 13/16

(

122

,

2

)

^

12 5/16

(312 7)

BLOWER ACCESS-

PANEL

RIGHT SIDE VIEW

BURNER AND CONTROL BOX

ACCESS PANEL

LEFT SIDE VIEW

REQ’D CLEARANCES FOR SERVICING in. (mm)

Duct panel

.0

Unit top

36(914)

Side opposite ducts

36(914)

Compressor access

36(914)

(Except for NEC requirements)

REQ’D CLEARANCES TO COMBUSTIBLE MAIL, in. (mm)

Maximum extension of overhangs

. .

48(1219)

Unit top........................... 14 (356)
Duct side of unit .

.

.

.

.

.

0

Side opposite ducts

9 (229)

Bottom of unit . .

.

.

.

.

. .

0

Flue panel

. .

30 (762)

NEC REQ’D CLEARANCES in. (mm)

Between units, control box side

42 (1067)

Unit and ungrounded surfaces, control box side

. 36 (914)

Unit and block or concrete walls and other grounded

surfaces, control box side .

.

.

.

.42(1067)

5/0- ^COMPRESSOR ACCESS PANEL

UNIT

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

CORNER WEIGHT

(Ib/kg)

lb

kg

A

B

C

D

48SX024040

208/230-1-60

333

151

104/47

50/23

130/59

49/22

48SX024060

208/230-1-60

345

157

107/49

53/24

133/60

52/24

48SX030040

208/230-1-60

336

153

97/44

66/30

118/54

55/25

48SX030060/080

208/230-1-60

348

158

100/45

69/31

121/55

58/26

48SX036060/080

208/230-1-60

366

166

94/43

84/38

117/53

71/32

48SX036100/120

208/230-1-60

378

172

97/44

87/40

120/55

74/34

UNIT

CENTER OF GRAVITY (in./mm)

X

Y

Z

48SX024040

26.71/678

20.06/510

12 65/321

48SX024060

26.64/677

20.12/511

12 65/321

48SX030040

27 06/687

21 05/535

12.65/321

48SX030060/080

26.98/685

21 07/535

12.65/321

48SX036060/080

27.14/689

21 10/536

12 65/321

48SX036100/120

27 06/687

21 12/536

12 65/321

LEGEND

CG — Center of Gravity

COND — Condenser
LV — Low Voltage

MAT’L - Material

NEC — National Electrical Code
REQ’D — Required

NOTE: Clearances must be maintained to prevent recirculation of
air from outdoor-fan discharge.

Fig. 6 — 48SX024-036 Without Base Rail, Unit Dimensions