Carrier 48SX024-048 User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

52

49 9/16"

(1320.8) (1259.3)

REQ'D CLEARANCES FOR SERVICING in (mm)

Duct panel
Unit top ... .
Siete opposite ducts
Compressor access
(Except for NEC requirements)

REQ'D CLEARANCES TO COMBUSTIBLE MATE in (mm)

0

36 (914)
36 (914)
36 (914)

Maximum extension of overhangs
Unit top
Duct side of unit .
Side opposite ducts
Bottom of unit
Flue panel..........................

NEC REQ’D CLEARANCES in. (mm)

Between units, control box side
Unit and ungrounded surfaces, control box side
Unit and block or concrete walls and other grounded
surfaces, control box side

7/8 (22.2) OIA
CONTROL ENTRY

48 (1219)

14 (356)

. 0

9 (229)

. . 0

30 (762)

42 (1067)

36 (914)

42 (1067)

OPTIONAL RETURN

AIR OPENING

1 11/16'

(43.2)

^1 13/16"

(46.2)

17 1/16 -

I (433.9)

^OPTIONAL SUPPLY

AIR OPENING

1 5/8 (41 3) OIA

GAS ENTRY

1/2" - 14 NPT

GAS CONNECTION

REAR VIEW

LEFT 510E VIEW

UNIT

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

CORNER WEIGHT

(Ib/kg)

lb

kg

A

B

C

D

48SX024040

208/230-1-60

357

163

110/50

56/25

136/62

55/25

48SX024060

208/230-1-60

369

168

113/51

59/27

139/63

58/26

48SX030040

208/230-1-60

360

164

103/47

72/33

124/56

61/28

48SX030060/080

208/230-1-60

372

169

106/48

75/34

127/58

64/29

48SX036060/080

208/230-1-60, 208/230-3-60, 460-3-60

390

177

100/45

90/41

123/56

77/35

48SX036100/120

208/230-1-60, 208/230-3-60, 460-3-60

402

183

103/47

93/42

127/57

80/36

UNIT

CENTER OF GRAVITY (In./mm)

X

Y

Z

48SX024040

26 57/674 9

20 17/512 3

14 96/380 0

48SX024060

26 51/673 3

20.22/513 6

14 96/380 0

48SX030040

26 90/683 3

21.09/535 7

14 96/380 0

48SX030060/080

26 83/681.5

21 11/536.2

14 96/380.0

48SX036060/080

26.99/685 5

21 14/537 0

14.96/380 0

48SX036100/120

26 92/683 8

21 14/537 0

14 96/380.0

LEGEND

CG

— Center of Gravity

MAT'L —

COND

— Condenser

NEC

LV

— Low Voltage

REQ’D —

Material
National Electrical Code

Required

NOTE: Clearances must be maintained to prevent recirculation of
air from outdoor-fan discharge

Fig. 7 — 48SX024-036 With Optional Base Rail, Unit Dimensions

Advertising