Table 4 — Electrical Data
UNIT
48SS
V-PH-HZ
VOLTAGE
COMPRESSOR
COND
FAN
INDOOR
POWER SUPPLY
AWG 60 C
MAX WIRE
RANGE
MOTOR
FAN
FLA
MIN WIRE
SIZE
LENGTH
(ft)
Min
Max
RLA
LRA
FLA
MCA
MOCP*
018
7.6
45.0
07
1 8
12.0
15
14
75
024
12.4
61.0
07
20
18.2
30
12
80
030
14.4
82.0
1 4
2.0
21.8
30
10
100
036
208/230-1-60
187
253
18.0
96.0
1 4
2.8
26 7
40
10
90
042
20.4
104 0
1.4
4.0
30.9
50
8
100
048
26.4
129 0
2.1
5.0
40.1
60
6
100
060
32.1
169 0
2.1
6.8
49.0
60
6
100
030
9.4
66 0
1.4
2.0
15.5
25
12
80
036
11 7
75.0
1.4
2.8
18.8
30
12
65
042
208/230-3-60
187
253
140
91 0
1.4
4.0
22.9
35
10
85
048
150
99 0
2.1
5.0
25.9
40
10
75
060
193
123.0
2.1
6.8
33.0
50
8
90
036
56
40 0
0.8
1.4
9.2
10
14
100
042
048
460-3-60
414
506
64
8.2
42 0
50 0
08
1.1
20
2.3
108
13.7
15
20
14
14
100
100
060
100
62 0
1.1
32
16.8
25
12
100
i
UNIT
48SX
024
030
036
042
048
208/230-1-60
187
253
12 9
150
16.7
20.0
26.4
62.5
76.0
95.0
104.0
129.0
1.4
1.4
1.4
1 4
1.4
2.0
2.6
2.8
3.1
5.0
19.5
22 8
25 1
29.5
39.4
30
30
30
45
60
12
10
10
10
8
75
100
95
80
90
036
10.9
75.0
1.4
2.8
17.8
25
12
70
042
208/230-3-60
187
253
13.9
88.0
1.4
3 1
21.9
30
10
60
048
15.0
99.0
1 4
50
25.2
40
10
80
036
5.4
40.0
0.8
1.4
9.0
10
14
100
042
460-3-60
414
506
6.8
44.0
0.8
1.6
10.9
15
14
100
048
8.2
49 5
0.8
2.3
134
20
14
100
LEGEND
AWG — American Wire Gage
COND — Condenser
FLA — Fail Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps
‘Fuse or HACR breaker
NOTES:
1. in compliance with NEC (Nationai Electricai Code) requirements
for muitimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker
2. Minimum wire size is based on 60 C copper wire, if other than
60 C wire is used, or if iength exceeds wire length in table, de
termine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt
age is greater than 2%. Use the following formula to determine
the percent of voltage imbalance.
% Veltage imbalance
^ .|QQj^
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
AB = 452
V
BC = 464
V
AC = 455
V
Average Voltage =
452 -H 464 -I- 455
3
1371
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 - 452 = 5
V
(BC) 464 - 457 = 7
V
(AC) 457 - 455 = 2
V
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x —^
457
= 1 53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
20