Table 4 — Electrical Data

UNIT

48SS

V-PH-HZ

VOLTAGE

COMPRESSOR

COND

FAN

INDOOR

POWER SUPPLY

AWG 60 C

MAX WIRE

RANGE

MOTOR

FAN

FLA

MIN WIRE

SIZE

LENGTH

(ft)

Min

Max

RLA

LRA

FLA

MCA

MOCP*

018

7.6

45.0

07

1 8

12.0

15

14

75

024

12.4

61.0

07

20

18.2

30

12

80

030

14.4

82.0

1 4

2.0

21.8

30

10

100

036

208/230-1-60

187

253

18.0

96.0

1 4

2.8

26 7

40

10

90

042

20.4

104 0

1.4

4.0

30.9

50

8

100

048

26.4

129 0

2.1

5.0

40.1

60

6

100

060

32.1

169 0

2.1

6.8

49.0

60

6

100

030

9.4

66 0

1.4

2.0

15.5

25

12

80

036

11 7

75.0

1.4

2.8

18.8

30

12

65

042

208/230-3-60

187

253

140

91 0

1.4

4.0

22.9

35

10

85

048

150

99 0

2.1

5.0

25.9

40

10

75

060

193

123.0

2.1

6.8

33.0

50

8

90

036

56

40 0

0.8

1.4

9.2

10

14

100

042

048

460-3-60

414

506

64

8.2

42 0
50 0

08

1.1

20

2.3

108

13.7

15
20

14
14

100
100

060

100

62 0

1.1

32

16.8

25

12

100

i

UNIT

48SX

024
030
036
042
048

208/230-1-60

187

253

12 9
150
16.7

20.0
26.4

62.5
76.0
95.0

104.0
129.0

1.4
1.4
1.4
1 4
1.4

2.0
2.6
2.8

3.1

5.0

19.5

22 8
25 1
29.5
39.4

30
30
30
45
60

12
10
10
10

8

75

100

95
80
90

036

10.9

75.0

1.4

2.8

17.8

25

12

70

042

208/230-3-60

187

253

13.9

88.0

1.4

3 1

21.9

30

10

60

048

15.0

99.0

1 4

50

25.2

40

10

80

036

5.4

40.0

0.8

1.4

9.0

10

14

100

042

460-3-60

414

506

6.8

44.0

0.8

1.6

10.9

15

14

100

048

8.2

49 5

0.8

2.3

134

20

14

100

LEGEND

AWG — American Wire Gage
COND — Condenser

FLA — Fail Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps
‘Fuse or HACR breaker
NOTES:
1. in compliance with NEC (Nationai Electricai Code) requirements

for muitimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the

unit shall be fuse or HACR breaker. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker

2. Minimum wire size is based on 60 C copper wire, if other than

60 C wire is used, or if iength exceeds wire length in table, de­
termine size from NEC.

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt­
age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance.

% Veltage imbalance

^ .|QQj^

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60.

AB = 452

V

BC = 464

V

AC = 455

V

Average Voltage =

452 -H 464 -I- 455

3

1371

3

= 457

Determine maximum deviation from average voltage.
(AB) 457 - 452 = 5

V

(BC) 464 - 457 = 7

V

(AC) 457 - 455 = 2

V

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x —^

457

= 1 53%

This amount of phase imbalance is satisfactory as it is below the

maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

20