Table 8d — superheat charging table, 48sx042 – Carrier 48SX024-048 User Manual

Page 35

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 8C — Superheat Charging Table, 48SX036

TEMP (F)

AIR ENT

EVAP AIR - CFM

1200

Evap Air — Ewb (F

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

21.3

21.3

21 3

21.3

22.0

22.6

23.3

23 5

23.7

23.8

23.3

22 8

70

SPH

19.3

19.3

193

193

20.2

21 2

22 2

22.3

22 5

22.6

22.0

21.5

75

SPH

17.2

172

17.2

17.2

18.5

197

21 0

21 1

21.3

21.4

20.7

20 1

80

SPH

13.6

13.6

13.6

13.6

15.1

166

18.0

18.5

18.9

19.3

19.4

19.5

85

SPH

10.1

10 1

10 1

10.1

11.7

134

15 0

15.8

165

173

18.1

19.0

90

SPH

6.5

6.5

6.5

6.5

8.8

11.2

135

14.6

157

168

17.2

17.6

95

SPH

*

*

*

*

60

90

120

13.4

148

162

16.2

16.2

100

SPH

*

*

*

*

*

*

60

8.7

11 4

14 1

14.9

15.6

105

SPH

*

*

*

*

*

*

8.0

12 1

13.6

15.1

110

SPH

*

*

*

*

*

*

‘k

*

10.0

11.5

13.0

115

SPH

*

*

*

*

*

*

*

*

*

8.0

9.5

11.0

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrig­

erant slugging may occur

Table 8D — Superheat Charging Table, 48SX042

TEMP (F)

AIR ENT

EVAP AIR - CFM

1400

Evap Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

23 9

23 9

23.9

23.9

24.4

24 9

25 5

25 8

26.1

26 5

25.6

24 7

70

SPH

21.9

21.9

21 9

21.9

22.4

22 9

23 4

23 7

24.1

24 5

24 0

23.5

75

SPH

198

19.8

198

19.8

20 3

20 8

21 3

21 7

22 0

22 4

22.4

22 4

80

SPH

16.3

163

16.3

163

17.9

19.6

21.3

21 5

21.7

21.8

21 8

21 8

85

SPH

12 7

12.7

127

12 7

15.6

18.4

21 3

21 3

21.3

21 3

21 3

21 3

90

SPH

9.2

9.2

92

9.2

12.0

14 9

178

187

19.7

20.8

20.8

20 8

95

SPH

56

5.6

5.6

56

8.5

11.3

14.2

16.2

182

20.2

20.2

20 2

100

SPH

*

*

*

*

k

80

106

13 1

156

18.1

18.9

19.6

105

SPH

*

*

*

*

k

*

7 1

10 1

13.1

16.1

17.6

19 1

110

SPH

*

k

*

k

k

k

k

70

105

14.0

15.5

170

115

SPH

*

k

*

*

*

*

*

k

8.0

12.0

13.5

15.0

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrig­

erant slugging may occur.

Table 8E — Superheat Charging Table, 48SX048

TEMP (F)

AIR ENT

EVAP AIR - CFM

1600

Evap Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

27 2

27.2

27.2

27.2

27.0

26.7

26.5

26.0

25.6

25 1

24 5

24.0

70

SPH

25 0

25.0

25.0

25.0

24.8

24 6

24.5

24.5

24.5

24 6

23.8

23.1

75

SPH

22 8

22 8

22 8

22.8

22.7

22 5

22.4

22 9

23.5

24.0

23.1

22.2

80

SPH

20 6

20 6

20.6

20.6

20.5

20 4

20.3

21.4

22.4

23.5

22 4

21.4

85

SPH

18.3

183

18.3

18.3

18.3

18.3

183

19.8

21.4

22.9

21 8

20.6

90

SPH

133

133

13.3

13.3

14.2

152

163

178

19 3

20.9

20 4

19.9

95

SPH

82

82

8.2

8.2

10.2

12 2

142

157

17.3

18.8

19.0

19.2

100

SPH

k

*

*

k

6.3

84

106

12 9

15.2

17.5

18.1

18 7

105

SPH

*

*

*

k

k

*

7 1

10 1

13.1

16.1

17.1

18 2

110

SPH

*

k

*

*

k

*

k

7 1

10.5

14.0

15.3

16.6

115

SPH

k

k

*

*

k

*

*

*

8 0

12.0

13 5

150

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrig­

erant slugging may occur.

35