Table 16 - Cooling Troubleshooting Chart

SYMPTOM

CAUSE

REMEDY

Compressor and
condenser fan will
not start.

Power failure

Call power company.

Fuse blown or circuit breaker tripped

Replaoe fuse or reset circuit breaker.

Defective thermostat, contactor, transformer,

or control relay

Replace component.

Insufficient line voltage

Determine cause and correct.

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not
start but condenser
fan runs.

Faulty wiring or loose connections in

compressor circuit

Check wiring and repair or replace.

Compressor motor burned out, seized, or
internal overload open

Determine cause. Replace compressor.

Defective run/start capacitor, overload,

start relay

Determine cause and replace.

One leg of 3-phase power dead

Replace fuse or reset circuit breaker.
Determine cause.

Three-phase scroll
compressor (Units
48SS048,060 and
48SX036-048 only)

makes excessive
noise, and there
may be a low pres­
sure differential.

Scroll compressor is rotating in the
wrong direction

Correct the direction of rotation by reversing the
3-phase power leads to the unit Shut down unit to
allow pressures to equalize.

Compressor cycles
(other than normally
satisfying
thermostat).

Refrigerant overcharge or undercharge

Reclaim refrigerant, evacuate system and
recharge to capacities shown on nameplate.

Defective compressor

Replace and determine cause.

Insufficient line voltage

Determine cause and correct.

Blocked condenser

Determine cause and correct.

Defective run/start capacitor, overload

or start relay

Determine cause and replace.

Defective thermostat

Replace thermostat.

Faulty condenser-fan motor or capacitor

Replace.

Restriction in refrigerant system

Locate restriction and remove.

Compressor
operates
continuously.

Dirty air filter

Replace filter.

Unit undersized for load

Decrease load or increase unit size.

Thermostat set too low

Reset thermostat.

Low refrigerant charge

Locate leak, repair and recharge.

Leaking valves in compressor

Replace compressor

Air in system

Reclaim refrigerant, evacuate system, and recharge.

Condenser coil dirty or restricted

Clean coil or remove restriction.

Excessive head
pressure.

Dirty air filter

Replace filter.

Dirty condenser coil

Clean coil.

Refrigerant overcharged

Reclaim excess refrigerant.

Air in system

Reclaim refrigerant, evacuate system, and recharge.

Condenser air restricted or air short-cycling

Determine cause and correct.

Head pressure too
low.

Low refrigerant charge

Check for leaks, repair and recharge.

Compressor valves leaking

Replace compressor.

Restriction in liquid tube

Remove restriction.

Excessive suction
pressure.

High heat load

Check for source and eliminate.

Compressor valves leaking

Replace compressor.

Refrigerant overcharged

Reclaim excess refrigerant.

Suction pressure
too low.

Dirty air filter

Replace filter.

Low refrigerant charge

Check for leaks, repair and recharge.

Metering device or low side restricted

Remove source of restriction.

Insufficient evaporator airflow

Inorease air quantity. Check filter — replace if
necessary.

Temperature too low in conditioned area

Reset thermostat.

Outdoor ambient below 40 F

Install low-ambient kit.

Field-installed filter-drier restricted

Replace.