Combustion air pressure system failure, Check combustion fan ok. service call, Slow closing gas valve – Bonaire Touchpad User Manual

Page 42: Reset, service call, Controls – installation / setup / commissioning

Advertising
background image

M

ULTI

-A

PPLIANCE

T

OUCH

P

AD

Controls – Installation / Setup / Commissioning

F

AULT

C

ODES

F

OR

H

IGH

E

FFICIENCY

,

M

ID

E

FFICIENCY

H

EATERS

Code No.

Fault Code

Diagnosis

00

No Activity

There has been no fault codes registered or the
control has not been coded to the unit.

01

Block Flue

Check flue cowl installed correctly

02

Pressure Switch fused closed

Service Call

03

Combustion air pressure system failure

Check combustion fan OK. Service call.

04

Room air over temperature (auto reset)

Check Minimum Fan Speed, Duct design

05

Controller electronic malfunction

Reset, Service Call

06

Slow closing gas valve

Reset, Service Call

07

Ignition failure

Check: - igniter works, flame sensor, gas supply. For

forced draft High Efficiency units also check blocked
flue and blocked condensate drain. Service Call

08

Gas Interruption

Check gas supply, Flame Sensor, Service Call

09

EEPROM failure

Reset, Service Call

11

Missed Transmission

Check loom integrity and connections

12

No Communication (Touch Pad Only)

Touchpad cannot detect unit – check loom integrity
and connections

15

No recorded fault codes








Bonaire Control Systems

Page 42