Setting the water level & bleed rate, Controls – installation / setup / commissioning – Bonaire Touchpad User Manual

Page 45

Advertising
background image

M

ULTI

-A

PPLIANCE

T

OUCH

P

AD

Controls – Installation / Setup / Commissioning

Setting the Water Management Systems Parameter Table.

To enter into the installer setup mode for the water management options use the following steps.

Step 1

Ensure the control is in the OFF
mode.

Step 2

A series of unseen icons must be
pressed

1. Press and hold the ZONE 4 (1) icon

allowing for a Triple BEEP followed by a
Single BEEP.

2. In quick succession press the unseen

APPLIANCE COOL (2) icon followed by
the HEAT (3) icon.

3. If successfully executed the area will

display tP:01.

4. If unsuccessful repeat 1 and 2 of STEP 2.

Step 3 Using

the

to

select

E:01 from the display

area.

Step 4

Press ENTER. The display will now change to 1:01.

Step 5

Using the

arrows, select the parameter to

be changed as per the Water Management Table. Press
ENTER.

Step 6

Using the

to change the value as per the

‘Water Management Table”. Press ENTER.

Step 7

To change more water management parameters repeat
Step 4 – 7.

Step 8

Press FINISH to exit.

Where multiple units have been connected to a single touchpad, this procedure will have to be repeated for
each of the units connected – E01, E02 etc.

S

ETTING THE

W

ATER

L

EVEL

&

B

LEED RATE

There are 3 diagnostic modes available for use of which Parameter 2 and 3 can be used to assist the
setting of water levels in the unit. See the table below.

Diagnostic Table

Installer Maintenance

Parameter

Value Duration


1

Rt

_ _ _ _ x 100

Unit Run Time

2

00

10 Minutes

Fill Valve

3

00

20 Minutes

Fill Valve & Pump