Controls – Installation / Setup / Commissioning

To enter into the installer maintenance / diagnostic mode to check water level and pump function, use the
following steps:-

Step 1

Ensure the control is in the OFF mode.

Step 2

A series of unseen icons must be pressed

1.

Press and hold the ZONE 4 (1) icon
allowing for a triple BEEP followed
by a BEEP.

2.

In quick succession press the
unseen APPLIANCE COOL (2)
icon 2 times.

If successfully executed the

numeric area will display tP 01.

3.

If unsuccessful repeat 1 and 2 of
STEP 2.

Step 3 Using

the

to

select

E:01 from

the numeric display area.

Step 4

Press ENTER. The display will now
change to 1 rt.

Step 5

Using the

arrows, select the

diagnostic 2 or 3 as per the Diagnostic
Table on this page. Press ENTER. 00 will
flash for the duration period.

Step 6

To exit the diagnostic, press ENTER.

Step 7

To select the other diagnostic parameter
repeat Step 5 & 6.

Step 8

Press FINISH to exit.

F

AN

S

PEED

S

ETTINGS

There are 2 available fan speed setting options for evaporative air conditioning as set out on the Fan
Speed Chart. Minimum fan speed should not go below 500 RPM else the fan motor will stop and start
because of over temping.
NOTE: fan speed settings should ONLY be set by a qualified installer or service technician

Fan Speed Chart

Installer
Maintenance

Parameter

Default Value

Range



Low Fan Speed

1

13

0 – 35

High Fan Speed

2

35

0 - 35

Bonaire Control Systems

Page 46