Technical features – CIRCUTOR QNA500 series User Manual

Page 107

Advertising
background image

POWER QUALITY ANALYZER QNA500 8IO

QNA500 8IO Instruction manual

107 / 111

13.- TECHNICAL FEATURES

AUXILIARY POWER SUPPLY (M-BASE)

Power Supply Voltage:

90-300VAC / 100-300VDC

Frequency:

50...60 Hz.

Consumption

:

11 VA (M-BASE)
5 VA (QNA500)
10 VA (M-8IO)

Working temperature:

-10...55ºC

Altitude

2000 m

AUXILIARY BATTERY POWER SUPPLY (M-BASE)

Battery:

Removable Ni-MH battery

Autonomy:

15 minutes of continuous operation (QNA500 8IO)

VOLTAGE MEASUREMENT (QNA500)

Measurement Circuit:

3 or 4-wire configuration

Measurement range :

0 to 500 VAC (phase-neutral),up to 866 VAC
(phase-phase)

Other voltages:

Through VT (Voltage transformers)

Maximum voltage of the permanent measurement: 1500 VAC (phase-phase)
Isolation voltage:

1.2/50 uS (8/20 uS) 6 kV

Frequency:

42.5 to 69 Hz

Sampling frequency :

512 samples/cycle

CURRENT MEASUREMENT (QNA500)

Measurement range:

1 to 120% of I

n

for I

n

= 5A

Maximum current:

120% of I

n

(for I

n

=5 A, I

max

=6 A) permanent, 100A

t<1 s

Sampling frequency:

512 samples/cycle

EARTH LEAKAGE CURRENT MEASUREMENT (ID) (QNA500)

Measurement range:

0-3 A

Maximum current:

3 A

Sampling frequency:

64 samples/cycle

DIGITAL INPUTS (M-8IO)

Type

Optocoupler

Working voltage:

12-18VDC

Isolation voltage:

5000V

Minimum width of the signal:

15 us

Consumption (per input)

2.5 mW

DIGITAL OUTPUTS (M-8IO)

Type:

SOLID STATE RELAY (OPTO-MOSFET)

Working voltage:

250 V

Working current:

130 mA

Isolation voltage :

3750V (between digital outputs and any other part
of the equipment – galvanic isolation)

Advertising