Connecting power supply – CIRCUTOR QNA500 series User Manual

Page 21

Advertising
background image

POWER QUALITY ANALYZER QNA500 8IO

QNA500 8IO Instruction manual

21 / 111

5.8.- CONNECTING POWER SUPPLY


The MULTIFIT system is powered with the M-BASE module. This power supply also powers all other
interconnected modules.

M-BASE power supply is powered with a connector with three terminals for power supply and
grounding purposes.

The equipment must be connected to a power circuit protected with gl-type
fuses, in compliance with IEC 269, or M-type, from 0.5 to 1A / 600 V (UL listed).
It must be fitted with a circuit breaker switch or equivalent device, in order to
be able to disconnect the device from the power supply. The power circuit and
voltage measurement circuits are connected with a cable with a minimum
cross-section of 1 mm

2

. (AWG 17). The current transformer's secondary

connection line must have a minimum cross-section of 2mm

2

. (AWG 14) and

withstand a minimum of 60ºC.

Advertising