UM022903-0311

ZAURA System Installation and Configuration

ZAURA

RF Wireless Lighting Control

Installation Guide

23

Light Detection Adjustment

The Master is preset to a dimming threshold that is appropriate for typical installations.
Due to variations in room characteristics, adjustments can be required to optimize dim-
ming performance. A Light Sensitivity POT is provided for adjusting the dimming thresh-
old. To access this sensitivity POT, the Master body must be removed from its base (as
described in the

Opening the Master Unit

section on page 16). Rotating the Light Sensitiv-

ity POT counterclockwise will increase the natural light level at which dimming occurs, as
shown in Figure 19.

Figure 18. Adjusting the Occupancy Sensitivity POT

Advertising