Refer to the, Associating a, Zaura starter with a master – Zilog ZAURCT User Manual

Page 36: Associating a zaura starter with a master

Advertising
background image

UM022903-0311

ZAURA System Installation and Configuration

ZAURA

RF Wireless Lighting Control

Installation Guide

30

If your installation will include both ZAURA Standard and Virtual Dimming Starters,
Zilog recommends that the installer mark at least one of these two types of starters for
tracking purposes. You may find a permanent marking pen to be suitable for this purpose.

Associating a ZAURA Starter with a Master

Before the ZAURA RF Wireless Lighting Control System can become operational,
ZAURA Starters are required to associate (i.e., be bound) to their Master. Both the Starter
and the Master must be triggered for association to occur. After they are associated, these
devices retain their associations even if power (line or battery) is removed.

Apply line power to the luminaries to trigger all unassociated Starters to seek a Master
until association completes or until line power is removed.

Do not apply power to unassociated ZAURA Starters in multiple rooms simultaneously
during association. Master communication range can be such that a Master in one room
can associate unintentionally with unassociated ZAURA Starters in another room. For
this reason, Zilog recommends performing complete installations and associations in one
room or area before moving on to the next room.

Do not trigger two Masters to associate simultaneously.

Observe the steps below to trigger only one master to associate.

1. Insert a battery into the Master battery receptacle, as shown in

Figure 20

on page 25.

2. Depress the

Associate Non-Dimmer

button on the Master until the green LED blinks

one time. Refer to

Figure 13

on page 18 for button location.

3. The Master will attempt association for a period of 30 seconds. If the

Associate Non-

Dimmer

button is depressed again during this 30-second period, a new 30-second

period of association is initiated. All powered and unassociated starters within range
will associate.

Each time a Starter becomes associated with the Master, the green LED on the Master will
blink.

Note:

Caution:

Caution: