Configuration tool method, Deassociating a range extender, Master method – Zilog ZAURCT User Manual

Page 42: Deassociating a, Range extender, See the

Advertising
background image

UM022903-0311

Reconfiguration of Masters and Starters

ZAURA

RF Wireless Lighting Control

Installation Guide

36

1. Turn off line power to the luminaries.

2. Place Starters in the luminaries.

3. Provide line power to the luminaries. Wait a minimum of three minutes for the starters

to resynchronize to the Master. Using the special

Toggle All

mode on the Master (see

the

Toggle All Lamps

section on page 19) can help determine when all of the starters

are synchronized to the Master.

4. Apply power to all Range Extenders, if any.

5. Depress both

Associate

buttons on the Master simultaneously for at least six seconds

until the blue LED illuminates.

6. Wait until the blue LED turns off before taking any other action with the system.

Configuration Tool Method

Using the Configuration Tool decommissions only one Starter at a time; however, it does
not reduce the number of Starters counted by the Master.

1. Plug in the Configuration tool.

2. Check that the Configuration Tool power switch is in the OFF position.

3. Place the ZAURA Starter into the Configuration Tool.

4. Place the Configuration Tool power switch in the ON position.

5. Wait four seconds. If a Master is triggered to associate while the Starter is in the

Configuration Tool, the Starter will associate to the Master.

6. Turn OFF the Configuration Tool power switch.

Deassociating a Range Extender

Should it become necessary to change the type or association of a Range Extender, the
Range Extender can be recommissioned by first deassociating it, then reassociating it as
required. Two methods exist to deassociate a Range Extender, the Master Method and the
Range Extender Method.

Master Method

The Master method deassociates all powered Starters and Range Extenders associated to
the Master. It is important to first provide power to all associated devices.

1. Ensure that all associated Range Extenders are powered on.

2. Depress both

Associate

buttons on the Master simultaneously for at least six seconds

until the blue LED illuminates.

3. Wait until the blue LED turns off before taking any other action with the system.

Advertising