Technical specifications – Zilog ZAURCT User Manual

Page 46

Advertising
background image

UM022903-0311

Technical Specifications

ZAURA

RF Wireless Lighting Control

Installation Guide

40

Technical Specifications

Table 1 lists a number of operating specifications for both the ZAURA Master and
ZAURA Starter.

Table 1. Technical Specifications for the ZAURA Master & Starter

ZAURA Master/Range Extender

ZAURA Starter

Environmental Conditions

Environmental Conditions

Storage Conditions

Storage Conditions

Temperature

20ºC to +55ºC

Temperature

15ºC to +85ºC

Relative Humidity

5%

90%; no

condensation

Relative Humidity

5%

95%; no

condensation

Operating Conditions

Operating Conditions

Temperature

+5ºC to +55ºC

Temperature

+5ºC to +85ºC

Relative Humidity

5%

90%; no

condensation

Relative Humidity

5%

90%; no

condensation

Power

Mains Connection

Battery

Lithium, 3 V Type CR123

Voltage

220 V

240 V

RMS

, 50 Hz

Battery life

Without Range
Extenders

>3 years (1 battery)

With Range Extenders >3 years (2 batteries)

As Range Extender

>3 years (1 battery)

Current Consumption

Power Consumption

0.1 W typical

Stand-by

~15 µA

Transmission

~26 mA

RF

RF

Frequency

865.6 MHz to 867.4 MHz

Frequency

865.6 MHz to 867.4 MHz

Modulation Type

FSK

Modulation Type

FSK

Radiated Power

~0.01 W

Radiated Power

~0.01 W

Range in Open Space 30m

Range in Open Space 30m

Receiver Class

3

Receiver Class

3

Duty Cycle

0.72 s/3600 s = 0.02%

Advertising
This manual is related to the following products: