Figure 34. Screen Configuration

Date and Time

The date and time of the IDP-800 must be set manually to match the date and time of the connected
DECS. Enter the desired values in the date and time fields and press the Change button to save the
values.

Records Duration

Trending records saved by the IDP-800 retain up to six variables per record with each record consisting of
2,400 data points. Trending records saved by the IDP-800 can have a user-defined duration ranging from
1 hour to 720 hours (30 days). Note: requires installation of a compact flash memory card.

Login Duration

Following login, the length of time that password access is available (if no button presses occur) is limited
by the value of this setting. If no button presses are received for the duration of the setting, password
access is lost and the user must log in again to make changes requiring password access. Login Duration
is adjustable over the range of 1 to 720 minutes (12 hours).

Screen Saver Delay

A screensaver activates if no button presses are received at the display panel for the length of time
specified by the Screen Saver Delay. A setting of 1 to 120 minutes may be entered.

Brightness

Display panel brightness can be adjusted by pressing the “+” and “–“ buttons. A bar graph above the
buttons serves as a reference for adjusting the display brightness.

Main View Screen

The Main View screen (Figure 35) serves as a gateway to the IDP-800 status and control screens. It also
provides access to file transfer functions and a screen lock to enable panel cleaning. The Login button
can be used to enter the appropriate password and gain access to the configuration screens.

Access to the control screens is possible only when logged into the IDP-800 with the correct password.
As a result, the Control button is visible only when logged into the IDP-800.

IDP-800-C Operation

IDP-800

Advertising