Decs-200n register tables, Decs-200n metering information category c2 – Basler Electric IDP-800 User Manual

Page 52

Advertising
background image

46

9437600990 Rev F

Register

Data Description

Access

Data Format

47711-12

Var maximum setpoint (in kvar) = % of nominal x rated gen.
VA:(regs. 47667-68) x rated VA / 100

R-

R32_23

47713-14

PF maximum setpoint = registers 47669-70

R-

R32_23

DECS-200N Register Tables

Three categories of DECS-200N information can be accessed through the IDP-800 using the Modbus
communication protocol: C2 (metering), C5 (operating modes), and C6 (setpoints).

DECS-200N Metering Information Category C2

Category C2 holding register assignments and descriptions are listed in Table 6.

Table 6. DECS-200N Metering Information Category C2

Register

Data Description

Access

Data Format

47257-58

Average of the three rms line-to-line voltages

R-

R32_23

47259-60

Generator current Ib in amps

R-

R32_23

47261-62

Generator apparent power in kVA

R-

R32_23

47263-64

Generator real power in kW

R-

R32_23

47265-66

Generator reactive power in kvar

R-

R32_23

47267-68

Power factor

R-

R32_23

47269-70

Generator frequency in hertz

R-

R32_23

47271-72

Bus frequency in hertz

R-

R32_23

47273-74

RMS bus voltage in volts

R-

R32_23

47275-76

Field voltage in volts

R-

R32_23

47277-78

Field current in amps

R-

R32_23

47283-84

Auxiliary input in volts (PSS input)

R-

R32_23

47287-88

Null balance (tracking error) in percent

R-

R32_23

47295

Status of the Front panel LEDs:
b0=Null Balance, b1=Internal Tracking, b2=Pre-Position,
b3=Upper Limit, b4=Lower Limit, b5=Edit Button

R-

UI16

47296

Voltage matching status: 0=off/1=on

R-

UI16

47297

Protection status bit flags (0=clear, 1=condition present):
b0=field over-voltage, b1=field over-current, b2=generator under-
voltage, b3=generator over-voltage, b4=under-frequency, b5=in
OEL, b6=in UEL, b7=in FCR mode, b8=loss of sensing voltage,
b9=setpoint at lower limit, b10=setpoint at upper limit, b11=
generator below 10Hz, b12=exciter diode open, b13=exciter diode
shorted, b14=loss of field, b15=in stator current limiting.

R-

UI16

47300-01

The active operating setpoint expressed as a percent of its
adjustment range.

R-

R32_23

47302

The state of some contact inputs: b0=52JK, b1=52LM, b2=Auto
Transfer, b3=Ext. Tracking Enable

R-

UI16

47303

Annunciation status bit flags (0=clear, 1=annunciation present):
b0=field over-voltage, b1=field over-current, b2=generator under-
voltage, b3=generator over-voltage, b4=under-frequency, b5=in
OEL, b6=in UEL, b7=in FCR mode, b8=loss of sensing voltage,
b9=setpoint at lower limit, b10=setpoint at upper limit, b11=
generator below 10 Hz, b12=exciter diode open, b13=exciter
diode shorted, b14=loss of field, b15=in stator current limiting.

R-

UI16

Modbus™ Communication