Application Guide TwinSAFE

2.23 Direct wiring of the TwinSAFE outputs to TwinSAFE

inputs (2-channel) (Category 3, PL d)

Two outputs of an EL2904 are wired directly to two safe inputs of an EL1904; the test pulses and current
measurement of the outputs and the sensor test of the inputs are thereby deactivated. On the input side,
both signals are checked for discrepancy within the TwinSAFE logic. Hence, both signals are checked for
their value, but no tests are active on the cable, so that possible external feeds are detected when
switching the outputs.

2.23.1 Parameters of the safe input and output terminals

EL1904

Parameter

Value

Sensor test channel 1 active

No

Sensor test channel 2 active

No

Sensor test channel 3 active

No

Sensor test channel 4 active

No

Logic channel 1 and 2

Single Logic

Logic channel 3 and 4

Single Logic

EL2904

Parameter

Value

Current measurement active

No

Output test pulses active

No

2.23.2 Block formation and safety loops

2.23.2.1 Block 1

EL6900

EL2904

EL2904

EL1904

EL2904

EL1904