2 block formation and safety loops, 3 calculation – BECKHOFF TwinSAFE User Manual

Page 40

Advertising
background image

Circuit examples

38

Application Guide TwinSAFE

EL2904

Parameter

Value

Current measurement active

No

Output test pulses active

No

2.6.2

Block formation and safety loops

2.6.2.1

Block 1

2.6.3

Calculation

2.6.3.1

PFH / MTTF

d

/B10

d

– values

Component

Value

EL1904 – PFH

1.11E-09

EL2904 – PFH

1.25E-09

EL6900 – PFH

1.03E-09

S1 – B10

d

100,000

S2 – B10

d

10,000,000

K1 – B10

d

1,300,000

K2 – B10

d

1,300,000

Days of operation (d

op

)

230

Hours of operation / day (h

op

)

16

Cycle time (minutes) (T

cycle

)

10080 (1x per week)

Lifetime (T1)

20 years = 175200 hours

2.6.3.2

Diagnostic Coverage DC

Component

Value

S1 with testing/plausibility

DC

avg

=99%

S2 with plausibility

DC

avg

=90%

K1/K2 without testing and with EDM via a safe
input

DC

avg

=90%

S1

EL1904

EL6900

EL2904

K1

K2

S2

EL1904

Advertising